Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of North Carolina, Charlotte |
---|---|
Assessment Year | 2023 |
Principal Product | Printed Labels |
NAICS | 323111 - Commercial Printing (except Screen and Books) |
SIC | 2759 - Commercial Printing, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 55 |
Plant Area (Sq.Ft.) | 21,500 |
Annual Production | 1,500,000 Thousand Feet |
Production Hrs. Annual | 7,488 |
Location (State) | SC |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $145,518 | 2,730,799 | kWh | $0.05 |
Electricity Demand | $142,210 | 7,202 | kW-months/year | $19.75 |
Electricity Fees | $3,893 | - | $ | - |
Natural Gas | $745 | 51 | MMBtu | $14.69 |
TOTAL ENERGY COSTS | $295,642 | |||
RECOMMENDED SAVINGS* | $63,721 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Usage | Electricity Usage | Electricity Demand | Water Usage | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $2,074 Cost: - |
$1,373 | 25,930 | $701 | 36 | - | - |
$1,373 25,930 kWh |
$701 36 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $1,363 Cost: - |
$1,363 | 25,755 | - | - | - | - |
$1,363 25,755 kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3111 HEAT WATER DURING OFF-PEAK PERIODS AND STORE FOR LATER USE |
Savings: $4,697 Cost: $8,400 |
$629 | 11,875 | $4,068 | 206 | - | - |
$629 11,875 kWh |
$4,068 206 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2612 USE COOLING TOWER WATER INSTEAD OF REFRIGERATION |
Savings: $21,990 Cost: $40,000 |
$15,408 | 291,045 | $7,582 | 384 | $(-1,000) | (-200,000) |
$15,408 291,045 kWh |
$7,582 384 kW-months/year |
$(-1,000) (-200,000) Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $33,597 Cost: $180,600 |
$19,380 | 366,080 | $14,217 | 720 | - | - |
$19,380 366,080 kWh |
$14,217 720 kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $63,721 Cost: $229,000 |
$38,153 | 720,685 | $26,568 | 1,346 | $(-1,000) | (-200,000) | $38,153 720,685 kWh |
$26,568 1,346 kW-months/year |
$(-1,000) (-200,000) Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Usage | Electricity Usage | Electricity Demand | Water Usage |