Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Colorado State University
Assessment Year 2006
Principal Product Breakfast cereals
NAICS 311230 - Breakfast Cereal Manufacturing
SIC 2043 - Cereal Breakfast Foods
Sales <$500,000
# of Employees 200
Plant Area (Sq.Ft.) 176,100
Annual Production 13,000,000 Pieces
Production Hrs. Annual 8,760
Location (State) NM
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,015,524 26,820,000 kWh $0.04
Electricity Demand $493,447 50,734 kW-months/year $9.73
Electricity Fees $68,434 - $ -
Natural Gas $1,494,479 149,959 MMBtu $9.97
TOTAL ENERGY COSTS $3,071,884
RECOMMENDED SAVINGS* $371,480 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $81,490
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Administrative Changes Electricity Usage Electricity Demand Natural Gas Administrative Changes
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT Savings:
$264,540
Cost:
$1,173,000
$186,670 4,943,300 $77,870 7,128 - - - - $186,670
4,943,300
kWh
$77,870
7,128
kW-months/year
-
-
MMBtu
-
-
$
02: 2.2692 USE OUTSIDE COLD WATER SOURCE AS A SUPPLY OF COOLING WATER Savings:
$56,580
Cost:
$570
$40,430 1,079,000 $16,150 1,478 - - - - $40,430
1,079,000
kWh
$16,150
1,478
kW-months/year
-
-
MMBtu
-
-
$
03: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$950
Cost:
$500
- - - - $950 96 - - -
-
kWh
-
-
kW-months/year
$950
96
MMBtu
-
-
$
04: 2.7233 USE PROPERLY DESIGNED AND SIZED HVAC EQUIPMENT Savings:
$23,960
Cost:
-
$17,120 456,800 $6,840 626 - - - - $17,120
456,800
kWh
$6,840
626
kW-months/year
-
-
MMBtu
-
-
$
05: 2.7252 UTILIZE AN EVAPORATIVE AIR PRE-COOLER OR OTHER HEAT EXCHANGER IN AC SYSTEM Savings:
$21,540
Cost:
$100,800
$11,050 322,600 $10,490 960 - - - - $11,050
322,600
kWh
$10,490
960
kW-months/year
-
-
MMBtu
-
-
$
06: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$3,910
Cost:
$32,600
$1,100 23,000 $870 80 - - $1,940 - $1,100
23,000
kWh
$870
80
kW-months/year
-
-
MMBtu
$1,940
-
$
TOTAL RECOMMENDED Savings:
$371,480
Cost:
$1,307,470
$256,370 6,824,700 $112,220 10,272 $950 96 $1,940 - $256,370
6,824,700
kWh
$112,220
10,272
kW-months/year
$950
96
MMBtu
$1,940
-
$
TOTAL IMPLEMENTED Savings:
$81,490
Cost:
$1,070
$57,550 1,535,800 $22,990 2,104 $950 96 - - $57,550
1,535,800
kWh
$22,990
2,104
kW-months/year
$950
96
MMBtu
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $
Electricity Usage Electricity Demand Natural Gas Administrative Changes Electricity Usage Electricity Demand Natural Gas Administrative Changes