Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Delaware |
---|---|
Assessment Year | 2008 |
Principal Product | Monomers, Polyester Acrylates,Sarbox |
NAICS | 325199 - All Other Basic Organic Chemical Manufacturing |
SIC | 2821 - Plastics Materials And Resins |
Sales | $100,000,000-$500,000,000 |
# of Employees | 95 |
Plant Area (Sq.Ft.) | 25,000 |
Annual Production | 1,000 Units |
Production Hrs. Annual | 6,000 |
Location (State) | PA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $502,960 | 9,370,590 | kWh | $0.05 |
Electricity Demand | $214,977 | 1,286 | kW-months/year | $167.17 |
Natural Gas | $1,241,710 | 127,804 | MMBtu | $9.72 |
Fuel Oil #2 | $578,359 | 38,502 | MMBtu | $15.02 |
TOTAL ENERGY COSTS | $2,656,684 | |||
RECOMMENDED SAVINGS* | $158,914 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $158,914 |
#|Description |
Savings Cost |
Status | Electricity Usage | Natural Gas | Electricity Usage | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $18,300 Cost: - |
$3,000 | 37,500 | $15,300 | 1,600 |
$3,000 37,500 kWh |
$15,300 1,600 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $2,396 Cost: $285 |
$2,396 | 29,952 | - | - |
$2,396 29,952 kWh |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $108,300 Cost: $104,800 |
- | - | $108,300 | 11,300 |
- - kWh |
$108,300 11,300 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.1243 USE HEAT FROM BOILER BLOWDOWN TO PREHEAT BOILER FEED WATER |
Savings: $24,218 Cost: $25,000 |
- | - | $24,218 | 2,528 |
- - kWh |
$24,218 2,528 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING |
Savings: $5,700 Cost: $10,000 |
$5,700 | 43,575 | - | - |
$5,700 43,575 kWh |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $158,914 Cost: $140,085 |
$11,096 | 111,027 | $147,818 | 15,428 | $11,096 111,027 kWh |
$147,818 15,428 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $158,914 Cost: $140,085 |
$11,096 | 111,027 | $147,818 | 15,428 | $11,096 111,027 kWh |
$147,818 15,428 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||