Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Delaware
Assessment Year 2013
Principal Product cooling towers
NAICS 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen
SIC 5075 - Warm Air Heating & Air-conditioning
Sales $50,000,000-$100,000,000
# of Employees 140
Plant Area (Sq.Ft.) 200,000
Annual Production 9,999,999 Units
Production Hrs. Annual 6,800
Location (State) DE
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $305,486 4,898,880 kWh $0.06
Electricity Demand $135,708 14,862 kW-months/year $9.13
Natural Gas $184,320 25,600 MMBtu $7.20
TOTAL ENERGY COSTS $625,514
RECOMMENDED SAVINGS* $152,766 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $71,950
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.7314 REDUCE VENTILATION AIR Savings:
$59,100
Cost:
$250,000
$2,940 31,000 $56,160 7,800 $2,940
31,000
kWh
$56,160
7,800
MMBtu
02: 2.7316 CENTRALIZE CONTROL OF EXHAUST FANS TO ENSURE THEIR SHUTDOWN, OR ESTABLISH PROGRAM TO ENSURE MANUAL SHUTDOWN Savings:
$25,000
Cost:
$45,000
$8,440 90,000 $16,560 2,300 $8,440
90,000
kWh
$16,560
2,300
MMBtu
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$28,900
Cost:
$200
$28,900 268,000 - - $28,900
268,000
kWh
-
-
MMBtu
04: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$14,700
Cost:
$100
$14,700 169,000 - - $14,700
169,000
kWh
-
-
MMBtu
05: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$8,606
Cost:
$440
$8,606 91,552 - - $8,606
91,552
kWh
-
-
MMBtu
06: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS Savings:
$6,746
Cost:
$4,200
- - $6,746 937 -
-
kWh
$6,746
937
MMBtu
07: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED Savings:
$6,364
Cost:
$180
$1,389 14,771 $4,975 691 $1,389
14,771
kWh
$4,975
691
MMBtu
08: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$2,200
Cost:
$100
$2,200 25,700 - - $2,200
25,700
kWh
-
-
MMBtu
09: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$1,150
Cost:
$494
$1,150 12,240 - - $1,150
12,240
kWh
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$152,766
Cost:
$300,714
$68,325 702,263 $84,441 11,728 $68,325
702,263
kWh
$84,441
11,728
MMBtu
TOTAL IMPLEMENTED Savings:
$71,950
Cost:
$45,894
$55,390 564,940 $16,560 2,300 $55,390
564,940
kWh
$16,560
2,300
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Natural Gas Electricity Usage Natural Gas