Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Delaware |
---|---|
Assessment Year | 2024 |
Principal Product | packaged dry food products |
NAICS | 311423 - Dried and Dehydrated Food Manufacturing |
SIC | 2099 - Food Preparations, Nec |
Sales | $1,000,000-$5,000,000 |
# of Employees | 592 |
Plant Area (Sq.Ft.) | 900,000 |
Annual Production | 107,000 Tons |
Production Hrs. Annual | 7,224 |
Location (State) | DE |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $3,123,752 | 43,731,684 | kWh | $0.07 |
Electricity Demand | $747,293 | 74,751 | kW-months/year | $10.00 |
Electricity Fees | $85,205 | - | $ | - |
Natural Gas | $417,861 | 62,550 | MMBtu | $6.68 |
Other Gas | $1,128,433 | 87,840 | MMBtu | $12.85 |
TOTAL ENERGY COSTS | $5,502,544 | |||
RECOMMENDED SAVINGS* | $885,725 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Other Gas | Electricity Usage | Electricity Demand | Natural Gas | Other Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $236,055 Cost: $1,860,000 |
$107,332 | 1,511,723 | $128,723 | 12,876 | - | - | - | - |
$107,332 1,511,723 kWh |
$128,723 12,876 kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $21,276 Cost: $7,300 |
$16,784 | 236,400 | $4,492 | 449 | - | - | - | - |
$16,784 236,400 kWh |
$4,492 449 kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $205,595 Cost: $34,400 |
$162,981 | 2,295,500 | $42,614 | 4,262 | - | - | - | - |
$162,981 2,295,500 kWh |
$42,614 4,262 kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2113 REPAIR OR REPLACE STEAM TRAPS |
Savings: $112,874 Cost: $37,000 |
- | - | - | - | - | - | $112,874 | 8,784 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$112,874 8,784 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $40,888 Cost: $180,000 |
- | - | - | - | - | - | $40,888 | 3,182 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$40,888 3,182 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $56,437 Cost: $22,000 |
- | - | - | - | - | - | $56,437 | 4,392 |
- - kWh |
- - kW-months/year |
- - MMBtu |
$56,437 4,392 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.1392 REPLACE PURCHASED STEAM WITH OTHER ENERGY SOURCE |
Savings: $212,600 Cost: $900,000 |
- | - | - | - | $(-916,144) | (-109,800) | $1,128,744 | 87,840 |
- - kWh |
- - kW-months/year |
$(-916,144) (-109,800) MMBtu |
$1,128,744 87,840 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $885,725 Cost: $3,040,700 |
$287,097 | 4,043,623 | $175,829 | 17,587 | $(-916,144) | (-109,800) | $1,338,943 | 104,198 | $287,097 4,043,623 kWh |
$175,829 17,587 kW-months/year |
$(-916,144) (-109,800) MMBtu |
$1,338,943 104,198 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Other Gas | Electricity Usage | Electricity Demand | Natural Gas | Other Gas |