IAC logo
IAC Assessment: GT0892
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: GT0892
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Georgia Institute of Technology
Assessment Year 2012
Principal Product HVAC Fan Coils
NAICS 333415 - Air-Conditioning and Warm Air Heating Equipment and Commercial and Industrial Refrigeration Equipmen
SIC 3585 - Refrigeration And Heating Equipment
Sales $50,000,000-$100,000,000
# of Employees 240
Plant Area (Sq.Ft.) 108,000
Annual Production 53,000 Pieces
Production Hrs. Annual 6,600
Location (State) GA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $218,215 3,698,565 kWh $0.06
Electricity Demand $174,513 9,531 kW-months/year $18.31
Electricity Fees $41,714 - $ -
Natural Gas $62,996 9,362 MMBtu $6.73
TOTAL ENERGY COSTS $497,438
RECOMMENDED SAVINGS* $96,505 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $15,828
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees Natural Gas Electricity Usage Electricity Demand Electricity Fees Natural Gas
$ kWh $ kW-months/year $ $ $ MMBtu
01: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE Savings:
$14,198
Cost:
-
- - - - $14,198 - - - -
-
kWh
-
-
kW-months/year
$14,198
-
$
-
-
MMBtu
02: 2.4312 IMPROVE LUBRICATION PRACTICES Savings:
$8,776
Cost:
-
$4,777 80,960 $3,999 218 - - - - $4,777
80,960
kWh
$3,999
218
kW-months/year
-
-
$
-
-
MMBtu
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$35,344
Cost:
$111,720
$19,085 323,467 $16,259 888 - - - - $19,085
323,467
kWh
$16,259
888
kW-months/year
-
-
$
-
-
MMBtu
04: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$5,679
Cost:
$29,200
$2,105 35,685 $623 34 - - $2,951 452 $2,105
35,685
kWh
$623
34
kW-months/year
-
-
$
$2,951
452
MMBtu
05: 2.1133 ADJUST BURNERS FOR EFFICIENT OPERATION Savings:
$1,630
Cost:
$1,000
- - - - - - $1,630 250 -
-
kWh
-
-
kW-months/year
-
-
$
$1,630
250
MMBtu
06: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$14,558
Cost:
$21,000
- - - - - - $14,558 2,230 -
-
kWh
-
-
kW-months/year
-
-
$
$14,558
2,230
MMBtu
07: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT Savings:
$16,320
Cost:
$82,800
$16,320 276,668 - - - - - - $16,320
276,668
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$96,505
Cost:
$245,720
$42,287 716,780 $20,881 1,140 $14,198 - $19,139 2,932 $42,287
716,780
kWh
$20,881
1,140
kW-months/year
$14,198
-
$
$19,139
2,932
MMBtu
TOTAL IMPLEMENTED Savings:
$15,828
Cost:
$1,000
- - - - $14,198 - $1,630 250 -
-
kWh
-
-
kW-months/year
$14,198
-
$
$1,630
250
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ $ $ MMBtu
Electricity Usage Electricity Demand Electricity Fees Natural Gas Electricity Usage Electricity Demand Electricity Fees Natural Gas