Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Univ. of Kansas |
---|---|
Assessment Year | 1996 |
Principal Product | Telescoping and Articulating Cranes |
NAICS | n/a |
SIC | 3591 - |
Sales | $50,000,000-$100,000,000 |
# of Employees | 370 |
Plant Area (Sq.Ft.) | 221,520 |
Annual Production | 1,200 Pieces |
Production Hrs. Annual | 6,720 |
Location (State) | NE |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $130,134 | 6,751,172 | kWh | $0.02 |
Electricity Demand | $150,967 | 15,310 | kW-months/year | $9.86 |
Natural Gas | $78,091 | 29,225 | MMBtu | $2.67 |
TOTAL ENERGY COSTS | $376,472 | |||
RECOMMENDED SAVINGS* | $45,303 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $37,233 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Other Liquid (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Other Liquid (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | gal | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.8142 DISTILL CONTAMINATED SOLVENTS FOR REUSE |
Savings: $23,485 Cost: $6,060 |
$(-755) | (-14,654) | - | - | $12,096 | 3,696 | $(-2,640) | - | - | - | $14,784 | - |
$(-755) (-14,654) kWh |
- - kW-months/year |
$12,096 3,696 gal |
$(-2,640) - $ |
- - $ |
$14,784 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 4.231 PURCHASE EQUIPMENT INSTEAD OF LEASING |
Savings: $8,070 Cost: $2,075 |
- | - | - | - | $(-2,850) | (-950) | $(-1,080) | - | $12,000 | - | - | - |
- - kWh |
- - kW-months/year |
$(-2,850) (-950) gal |
$(-1,080) - $ |
$12,000 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $4,367 Cost: $7,650 |
- | - | $4,367 | - | - | - | - | - | - | - | - | - |
- - kWh |
$4,367 - kW-months/year |
- - gal |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,980 Cost: $236 |
$1,998 | 112,837 | $1,982 | 201 | - | - | - | - | - | - | - | - |
$1,998 112,837 kWh |
$1,982 201 kW-months/year |
- - gal |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $2,938 Cost: $556 |
$1,473 | 83,236 | $1,465 | 149 | - | - | - | - | - | - | - | - |
$1,473 83,236 kWh |
$1,465 149 kW-months/year |
- - gal |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,642 Cost: $1,500 |
$601 | 33,998 | $1,041 | 106 | - | - | - | - | - | - | - | - |
$601 33,998 kWh |
$1,041 106 kW-months/year |
- - gal |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $821 Cost: $299 |
$342 | 19,343 | $345 | 35 | - | - | - | - | - | - | $134 | - |
$342 19,343 kWh |
$345 35 kW-months/year |
- - gal |
- - $ |
- - $ |
$134 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $45,303 Cost: $18,376 |
$3,659 | 234,760 | $9,200 | 491 | $9,246 | 2,746 | $(-3,720) | - | $12,000 | - | $14,918 | - | $3,659 234,760 kWh |
$9,200 491 kW-months/year |
$9,246 2,746 gal |
$(-3,720) - $ |
$12,000 - $ |
$14,918 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $37,233 Cost: $16,301 |
$3,659 | 234,760 | $9,200 | 491 | $12,096 | 3,696 | $(-2,640) | - | - | - | $14,918 | - | $3,659 234,760 kWh |
$9,200 491 kW-months/year |
$12,096 3,696 gal |
$(-2,640) - $ |
- - $ |
$14,918 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | gal | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Other Liquid (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Other Liquid (haz) | Personnel Changes | Administrative Changes | Ancillary Material Cost |