Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Massachusetts
Assessment Year 2009
Principal Product Optical components and assemblies
NAICS 333314 - Optical Instrument and Lens Manufacturing
SIC 3827 - Optical Instruments And Lenses
Sales $10,000,000-$50,000,000
# of Employees 146
Plant Area (Sq.Ft.) 100,000
Annual Production 728,000 Pieces
Production Hrs. Annual 6,240
Location (State) NH
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $506,130 3,794,682 kWh $0.13
Electricity Demand $51,671 7,406 kW-months/year $6.98
Electricity Fees $20,682 - $ -
Natural Gas $7,812 303 MMBtu $25.78
LPG $184,573 7,544 MMBtu $24.47
TOTAL ENERGY COSTS $770,868
RECOMMENDED SAVINGS* $32,506 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $10,132
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas LPG Electricity Usage Electricity Demand Natural Gas LPG
$ kWh $ kW-months/year $ MMBtu $ MMBtu
01: 2.7311 VENTILATION SYSTEM TO SHUT OFF WHEN ROOM IS NOT IN USE Savings:
$11,122
Cost:
$1,990
$495 3,614 - - - - $10,627 435 $495
3,614
kWh
-
-
kW-months/year
-
-
MMBtu
$10,627
435
MMBtu
02: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$10,132
Cost:
$23,474
$10,132 73,953 - - - - - - $10,132
73,953
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
MMBtu
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$7,667
Cost:
-
$5,927 43,264 $1,740 250 - - - - $5,927
43,264
kWh
$1,740
250
kW-months/year
-
-
MMBtu
-
-
MMBtu
04: 2.7228 AVOID INTRODUCING HOT, HUMID, OR DIRTY AIR INTO HVAC SYSTEM Savings:
$3,585
Cost:
$6,600
$1,900 13,866 - - $1,685 69 - - $1,900
13,866
kWh
-
-
kW-months/year
$1,685
69
MMBtu
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$32,506
Cost:
$32,064
$18,454 134,697 $1,740 250 $1,685 69 $10,627 435 $18,454
134,697
kWh
$1,740
250
kW-months/year
$1,685
69
MMBtu
$10,627
435
MMBtu
TOTAL IMPLEMENTED Savings:
$10,132
Cost:
$23,474
$10,132 73,953 - - - - - - $10,132
73,953
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ MMBtu
Electricity Usage Electricity Demand Natural Gas LPG Electricity Usage Electricity Demand Natural Gas LPG