IAC Center University of Massachusetts
Assessment Year 2015
Principal Product Lighting fixtures
NAICS 335122 - Commercial, Industrial, and Institutional Electric Lighting Fixture Manufacturing
SIC 3646 - Commercial Lighting Fixtures
Sales $6,900,000
# of Employees 385
Plant Area (Sq.Ft.) 315,000
Annual Production 1,800,000 Pieces
Production Hrs. Annual 2,522
Location (State) MA
Source Yearly Cost Usage
Electricity Usage $655,278 5,759,778
Electricity Demand $118,309 21,552
Electricity Fees $(-1,123) -
Natural Gas $631,714 47,704
TOTAL ENERGY COSTS $1,404,178
RECOMMENDED SAVINGS* $114,521 *Non-energy impacts
included in savings.
IMPLEMENTED SAVINGS* $90,318
#|Description Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW/month $ MMBtu
01: 2.7315 REDUCE BUILDING VENTILATION AIR TO MINIMUM SAFE LEVELS Savings:
$30,757
Cost:
$20,400
$21,583 189,659 - - $9,174 703 $21,583
189,659
kWh
-
-
kW/month
$9,174
703
MMBtu
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$24,207
Cost:
$1,000
$24,207 212,716 - - - - $24,207
212,716
kWh
-
-
kW/month
-
-
MMBtu
03: 2.4141 USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS Savings:
$17,980
Cost:
$3,330
$17,980 157,997 - - - - $17,980
157,997
kWh
-
-
kW/month
-
-
MMBtu
04: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$10,366
Cost:
$25,300
- - $10,366 2,644 - - -
-
kWh
$10,366
2,644
kW/month
-
-
MMBtu
05: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$8,523
Cost:
$1,000
$1,659 14,575 - - $6,864 526 $1,659
14,575
kWh
-
-
kW/month
$6,864
526
MMBtu
06: 2.4141 USE MULTIPLE SPEED MOTORS OR AFD FOR VARIABLE PUMP, BLOWER AND COMPRESSOR LOADS Savings:
$6,856
Cost:
$24,500
$6,856 60,242 - - - - $6,856
60,242
kWh
-
-
kW/month
-
-
MMBtu
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$6,067
Cost:
$3,000
$6,067 53,315 - - - - $6,067
53,315
kWh
-
-
kW/month
-
-
MMBtu
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,495
Cost:
$500
$2,495 21,927 - - - - $2,495
21,927
kWh
-
-
kW/month
-
-
MMBtu
09: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$3,372
Cost:
$1,000
$3,372 29,635 - - - - $3,372
29,635
kWh
-
-
kW/month
-
-
MMBtu
10: 2.6121 REDUCE HOT WATER TEMPERATURE TO THE MINIMUM REQUIRED Savings:
$1,592
Cost:
$500
- - - - $1,592 122 -
-
kWh
-
-
kW/month
$1,592
122
MMBtu
11: 2.2131 INSULATE STEAM / HOT WATER LINES Savings:
$1,227
Cost:
$1,013
- - - - $1,227 94 -
-
kWh
-
-
kW/month
$1,227
94
MMBtu
12: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$1,079
Cost:
$100
$400 3,518 - - $679 52 $400
3,518
kWh
-
-
kW/month
$679
52
MMBtu
TOTAL RECOMMENDED Savings:
$114,521
Cost:
$81,643
$84,619 743,584 $10,366 2,644 $19,536 1,497 -
-
kWh
-
-
kW/month
-
-
MMBtu
TOTAL IMPLEMENTED Savings:
$90,318
Cost:
$53,330
$80,465 707,082 - - $9,853 755 -
-
kWh
-
-
kW/month
-
-
MMBtu
$ kWh $ kW/month $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
Back to Top