Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Massachusetts |
---|---|
Assessment Year | 2022 |
Principal Product | Roller Chains |
NAICS | 333613 - Mechanical Power Transmission Equipment Manufacturing |
SIC | 3568 - Power Transmission Equipment, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 175 |
Plant Area (Sq.Ft.) | 209,100 |
Annual Production | 4,000,000 Pounds |
Production Hrs. Annual | 8,760 |
Location (State) | MA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $526,026 | 5,705,760 | kWh | $0.09 |
Electricity Demand | $81,464 | 11,825 | kW-months/year | $6.89 |
Electricity Fees | $3,765 | - | $ | - |
Natural Gas | $514,325 | 61,679 | MMBtu | $8.34 |
TOTAL ENERGY COSTS | $1,133,951 | |||
RECOMMENDED SAVINGS* | $178,093 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $37,422 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $108,785 Cost: $906,122 |
$103,584 | 1,125,905 | $5,201 | 755 | - | - |
$103,584 1,125,905 kWh |
$5,201 755 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2523 REDUCE INFILTRATION TO REFRIGERATED AREAS; ISOLATE HOT EQUIPMENT FROM REFRIGERATED AREAS |
Savings: $26,668 Cost: $60,000 |
- | - | - | - | $26,668 | 3,198 |
- - kWh |
- - kW-months/year |
$26,668 3,198 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT |
Savings: $13,709 Cost: $182,139 |
$18,560 | 201,743 | $1,904 | 276 | $(-6,755) | (-810) |
$18,560 201,743 kWh |
$1,904 276 kW-months/year |
$(-6,755) (-810) MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $10,754 Cost: $14,292 |
$10,754 | 116,891 | - | - | - | - |
$10,754 116,891 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6122 ADJUST VENTS TO MINIMIZE ENERGY USE |
Savings: $8,349 Cost: $10,667 |
$8,349 | 90,750 | - | - | - | - |
$8,349 90,750 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $6,066 Cost: $2,910 |
$5,501 | 59,792 | $565 | 82 | - | - |
$5,501 59,792 kWh |
$565 82 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME |
Savings: $3,762 Cost: $505 |
$3,411 | 37,081 | $351 | 51 | - | - |
$3,411 37,081 kWh |
$351 51 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $178,093 Cost: $1,176,635 |
$150,159 | 1,632,162 | $8,021 | 1,164 | $19,913 | 2,388 | $150,159 1,632,162 kWh |
$8,021 1,164 kW-months/year |
$19,913 2,388 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $37,422 Cost: $74,292 |
$10,754 | 116,891 | - | - | $26,668 | 3,198 | $10,754 116,891 kWh |
- - kW-months/year |
$26,668 3,198 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |