Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Miami
Assessment Year 2015
Principal Product High Volume Hydraulic Cartridges
NAICS 332919 - Other Metal Valve and Pipe Fitting Manufacturing
SIC 3492 - Fluid Power Valves & Hose Fittings
Sales $50,000,000-$100,000,000
# of Employees 267
Plant Area (Sq.Ft.) 70,000
Annual Production 1,560,000 Pieces
Production Hrs. Annual 8,008
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $286,894 6,196,745 kWh $0.05
Electricity Demand $153,550 12,347 kW-months/year $12.44
Electricity Fees $23,197 - $ -
TOTAL ENERGY COSTS $463,640
RECOMMENDED SAVINGS* $69,185 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $33,804
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD Savings:
$19,094
Cost:
$29,862
$19,094 415,068 - - $19,094
415,068
kWh
-
-
kW-months/year
02: 2.7292 LOWER CEILING TO REDUCE CONDITIONED SPACE Savings:
$14,710
Cost:
$100,350
$14,710 319,780 - - $14,710
319,780
kWh
-
-
kW-months/year
03: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$12,602
Cost:
$80
$12,602 273,995 - - $12,602
273,995
kWh
-
-
kW-months/year
04: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$7,447
Cost:
$6,660
$5,296 115,131 $2,151 173 $5,296
115,131
kWh
$2,151
173
kW-months/year
05: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT Savings:
$5,778
Cost:
$4,691
$2,644 57,487 $3,134 252 $2,644
57,487
kWh
$3,134
252
kW-months/year
06: 2.7496 INSTALL PARTITIONS TO REDUCE SIZE OF CONDITIONED SPACE Savings:
$3,819
Cost:
$11,872
$3,819 83,017 - - $3,819
83,017
kWh
-
-
kW-months/year
07: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$3,433
Cost:
$5,370
$1,381 30,025 $2,052 165 $1,381
30,025
kWh
$2,052
165
kW-months/year
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,382
Cost:
$40
$636 13,823 $746 60 $636
13,823
kWh
$746
60
kW-months/year
09: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$920
Cost:
$1,670
$472 10,267 $448 36 $472
10,267
kWh
$448
36
kW-months/year
TOTAL RECOMMENDED Savings:
$69,185
Cost:
$160,595
$60,654 1,318,593 $8,531 686 $60,654
1,318,593
kWh
$8,531
686
kW-months/year
TOTAL IMPLEMENTED Savings:
$33,804
Cost:
$130,212
$33,804 734,848 - - $33,804
734,848
kWh
-
-
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand