Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Miami |
---|---|
Assessment Year | 2017 |
Principal Product | Electrical Terminals |
NAICS | 335931 - Current-Carrying Wiring Device Manufacturing |
SIC | 3643 - Current-carrying Wiring Devices |
Sales | $50,000,000-$100,000,000 |
# of Employees | 157 |
Plant Area (Sq.Ft.) | 45,000 |
Annual Production | 1,500,000 Units |
Production Hrs. Annual | 6,240 |
Location (State) | PR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $409,913 | 2,743,118 | kWh | $0.15 |
Electricity Demand | $79,453 | 8,172 | kW-months/year | $9.72 |
Electricity Fees | $8,126 | - | $ | - |
TOTAL ENERGY COSTS | $497,492 | |||
RECOMMENDED SAVINGS* | $266,229 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $194,732 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Administrative Changes | Electricity Usage | Electricity Demand | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2628 UTILIZE A LESS EXPENSIVE COOLING METHOD |
Savings: $58,668 Cost: $31,800 |
$47,860 | 321,205 | $6,008 | 618 | $4,800 | - |
$47,860 321,205 kWh |
$6,008 618 kW-months/year |
$4,800 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA |
Savings: $58,406 Cost: $120 |
$51,896 | 348,295 | $6,510 | 670 | - | - |
$51,896 348,295 kWh |
$6,510 670 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $53,871 Cost: $1,660 |
$46,959 | 315,164 | $6,912 | 712 | - | - |
$46,959 315,164 kWh |
$6,912 712 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $40,560 Cost: $27,600 |
$36,039 | 241,872 | $4,521 | 465 | - | - |
$36,039 241,872 kWh |
$4,521 465 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $23,860 Cost: $3,600 |
$23,860 | 160,136 | - | - | - | - |
$23,860 160,136 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $18,035 Cost: $23,565 |
- | - | $18,035 | 1,795 | - | - |
- - kWh |
$18,035 1,795 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $7,588 Cost: $2,300 |
$6,742 | 45,250 | $846 | 87 | - | - |
$6,742 45,250 kWh |
$846 87 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7245 USE DIRECT AIR SUPPLY TO EXHAUST HOODS |
Savings: $3,716 Cost: $6,530 |
$3,302 | 22,159 | $414 | 43 | - | - |
$3,302 22,159 kWh |
$414 43 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS |
Savings: $1,100 Cost: $2,272 |
$978 | 6,562 | $122 | 13 | - | - |
$978 6,562 kWh |
$122 13 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $425 Cost: $134 |
$328 | 2,199 | $97 | 10 | - | - |
$328 2,199 kWh |
$97 10 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $266,229 Cost: $99,581 |
$217,964 | 1,462,842 | $43,465 | 4,413 | $4,800 | - | $217,964 1,462,842 kWh |
$43,465 4,413 kW-months/year |
$4,800 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $194,732 Cost: $56,545 |
$158,754 | 1,065,467 | $35,978 | 3,642 | - | - | $158,754 1,065,467 kWh |
$35,978 3,642 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Administrative Changes | Electricity Usage | Electricity Demand | Administrative Changes |