IAC logo
IAC Assessment: MI0432
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: MI0432
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Miami
Assessment Year 2023
Principal Product Cosmetics & Skin Care Products Manufacturing
NAICS 325620 - Toilet Preparation Manufacturing
SIC 2844 - Toilet Preparations
Sales $50,000,000-$100,000,000
# of Employees 115
Plant Area (Sq.Ft.) 75,000
Annual Production 25,000,000 Pieces
Production Hrs. Annual 2,354
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $36,445 540,611 kWh $0.07
Electricity Demand $31,388 2,561 kW-months/year $12.26
Electricity Fees $15,659 - $ -
Natural Gas $22,606 1,861 MMBtu $12.15
TOTAL ENERGY COSTS $106,098
RECOMMENDED SAVINGS* $21,200 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $10,372
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$7,559
Cost:
$3,360
$7,559 112,819 - - - - $7,559
112,819
kWh
-
-
kW-months/year
-
-
MMBtu
02: 2.7221 LOWER TEMPERATURE DURING THE WINTER SEASON AND VICE-VERSA Savings:
$2,607
Cost:
$580
$2,085 31,124 $522 43 - - $2,085
31,124
kWh
$522
43
kW-months/year
-
-
MMBtu
03: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD Savings:
$2,131
Cost:
$6,528
$1,704 25,433 $427 35 - - $1,704
25,433
kWh
$427
35
kW-months/year
-
-
MMBtu
04: 2.7316 CENTRALIZE CONTROL OF EXHAUST FANS TO ENSURE THEIR SHUTDOWN, OR ESTABLISH PROGRAM TO ENSURE MANUAL SHUTDOWN Savings:
$2,728
Cost:
$1,750
$1,414 21,099 $1,314 107 - - $1,414
21,099
kWh
$1,314
107
kW-months/year
-
-
MMBtu
05: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO Savings:
$2,587
Cost:
$1,360
- - - - $2,587 213 -
-
kWh
-
-
kW-months/year
$2,587
213
MMBtu
06: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$1,952
Cost:
$120
$1,180 17,606 $772 63 - - $1,180
17,606
kWh
$772
63
kW-months/year
-
-
MMBtu
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$682
Cost:
$1,953
$412 6,152 $270 22 - - $412
6,152
kWh
$270
22
kW-months/year
-
-
MMBtu
08: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$678
Cost:
$490
- - - - $678 56 -
-
kWh
-
-
kW-months/year
$678
56
MMBtu
09: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$276
Cost:
$1,150
$144 2,117 $132 11 - - $144
2,117
kWh
$132
11
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$21,200
Cost:
$17,291
$14,498 216,350 $3,437 280 $3,265 269 $14,498
216,350
kWh
$3,437
280
kW-months/year
$3,265
269
MMBtu
TOTAL IMPLEMENTED Savings:
$10,372
Cost:
$11,841
$9,675 144,404 $697 57 - - $9,675
144,404
kWh
$697
57
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas