Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Mississippi State |
---|---|
Assessment Year | 1999 |
Principal Product | Compression Molded Drain Pans |
NAICS | n/a |
SIC | 3089 - Plastics Products, Nec |
Sales | $1,000,000-$5,000,000 |
# of Employees | 65 |
Plant Area (Sq.Ft.) | 840,000 |
Annual Production | 840,000 Pieces |
Production Hrs. Annual | 7,488 |
Location (State) | MS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $49,435 | 1,315,944 | kWh | $0.04 |
Electricity Demand | $23,981 | 3,336 | kW-months/year | $7.19 |
Electricity Fees | $3,698 | - | $ | - |
Natural Gas | $1,675 | 301 | MMBtu | $5.56 |
TOTAL ENERGY COSTS | $79,946 | |||
RECOMMENDED SAVINGS* | $19,130 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $8,866 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $2,236 Cost: $2,610 |
- | - | - | - | $2,236 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$2,236 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $50 Cost: $119 |
$49 | 1,465 | - | - | $1 | - | - | - | - | - |
$49 1,465 kWh |
- - kW-months/year |
$1 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7134 USE PHOTOCELL CONTROLS |
Savings: $276 Cost: $222 |
$272 | 8,206 | - | - | $4 | - | - | - | - | - |
$272 8,206 kWh |
- - kW-months/year |
$4 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $635 Cost: $89 |
$328 | 9,965 | $297 | 31 | $10 | - | - | - | - | - |
$328 9,965 kWh |
$297 31 kW-months/year |
$10 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $192 Cost: $346 |
$189 | 5,569 | - | - | $3 | - | - | - | - | - |
$189 5,569 kWh |
- - kW-months/year |
$3 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $4,736 Cost: $4,200 |
$4,666 | 140,680 | - | - | $70 | - | - | - | - | - |
$4,666 140,680 kWh |
- - kW-months/year |
$70 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $2,189 Cost: $2,446 |
$2,157 | 46,600 | - | - | $32 | - | - | - | - | - |
$2,157 46,600 kWh |
- - kW-months/year |
$32 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 3.7196 USE RE-USABLE FILTERS |
Savings: $4,800 Cost: $648 |
- | - | - | - | - | - | - | - | $4,800 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
$4,800 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 4.821 PAY BILLS ON TIME TO AVOID LATE FEES |
Savings: $16 Cost: - |
- | - | - | - | - | - | - | - | $16 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
$16 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 4.444 INSTALL SYSTEM TO COLLECT SCRAP |
Savings: $4,000 Cost: $5,246 |
- | - | - | - | - | - | $4,000 | - | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$4,000 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $19,130 Cost: $15,926 |
$7,661 | 212,485 | $297 | 31 | $2,356 | - | $4,000 | - | $4,816 | - | $7,661 212,485 kWh |
$297 31 kW-months/year |
$2,356 - $ |
$4,000 - $ |
$4,816 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $8,866 Cost: $6,013 |
$49 | 1,465 | - | - | $1 | - | $4,000 | - | $4,816 | - | $49 1,465 kWh |
- - kW-months/year |
$1 - $ |
$4,000 - $ |
$4,816 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost |