Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Mississippi State |
---|---|
Assessment Year | 2024 |
Principal Product | Specialty Elastomers |
NAICS | 325212 - Synthetic Rubber Manufacturing |
SIC | 2822 - Synthetic Rubber |
Sales | $10,000,000-$50,000,000 |
# of Employees | 36 |
Plant Area (Sq.Ft.) | 618,000 |
Annual Production | 9,000,000 Pounds |
Production Hrs. Annual | 8,400 |
Location (State) | MS |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $184,357 | 9,296,494 | kWh | $0.02 |
Electricity Demand | $132,145 | 16,572 | kW-months/year | $7.97 |
Electricity Fees | $365,680 | - | $ | - |
Natural Gas | $824,043 | 168,862 | MMBtu | $4.88 |
LPG | $59,685 | 1,870 | MMBtu | $31.91 |
TOTAL ENERGY COSTS | $1,565,910 | |||
RECOMMENDED SAVINGS* | $119,409 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Water Usage | Electricity Usage | Electricity Demand | LPG | Water Usage | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $60,065 Cost: $1,274,840 |
$34,938 | 1,746,888 | $25,127 | 3,135 | - | - | - | - |
$34,938 1,746,888 kWh |
$25,127 3,135 kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.1321 REPLACE FOSSIL FUEL EQUIPMENT WITH ELECTRICAL EQUIPMENT |
Savings: $57,233 Cost: $175,000 |
$(-2,452) | (-122,640) | - | - | $59,685 | 1,870 | - | - |
$(-2,452) (-122,640) kWh |
- - kW-months/year |
$59,685 1,870 MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 3.3127 USE ADSORPTION, ION EXCHANGE TO REMOVE CONTAMINANTS |
Savings: $2,111 Cost: $124,000 |
$2,099 | 105,870 | - | - | - | - | $12 | 2 |
$2,099 105,870 kWh |
- - kW-months/year |
- - MMBtu |
$12 2 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $119,409 Cost: $1,573,840 |
$34,585 | 1,730,118 | $25,127 | 3,135 | $59,685 | 1,870 | $12 | 2 | $34,585 1,730,118 kWh |
$25,127 3,135 kW-months/year |
$59,685 1,870 MMBtu |
$12 2 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | LPG | Water Usage | Electricity Usage | Electricity Demand | LPG | Water Usage |