Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Michigan State University |
---|---|
Assessment Year | 2023 |
Principal Product | Fiberglass Boats |
NAICS | 336612 - Boat Building |
SIC | 3732 - Boat Building And Repairing |
Sales | $100,000,000-$500,000,000 |
# of Employees | 200 |
Plant Area (Sq.Ft.) | 157,000 |
Annual Production | 1,200 Units |
Production Hrs. Annual | 3,640 |
Location (State) | MI |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $100,686 | 2,825,521 | kWh | $0.04 |
Electricity Demand | $252,379 | 8,212 | kW-months/year | $30.73 |
Electricity Fees | $24,840 | - | $ | - |
Natural Gas | $136,693 | 64,214 | MMBtu | $2.13 |
TOTAL ENERGY COSTS | $514,598 | |||
RECOMMENDED SAVINGS* | $165,679 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $157,264 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.1123 INSTALL AUTOMATIC STACK DAMPER |
Savings: $4,161 Cost: $959 |
- | - | - | - | $4,161 | 1,953 | - | - |
- - kWh |
- - kW-months/year |
$4,161 1,953 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER |
Savings: $1,074 Cost: $844 |
- | - | - | - | $1,074 | 504 | - | - |
- - kWh |
- - kW-months/year |
$1,074 504 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $26,806 Cost: $25,843 |
$(-1,052) | (-26,288) | - | - | $27,858 | 13,079 | - | - |
$(-1,052) (-26,288) kWh |
- - kW-months/year |
$27,858 13,079 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $11,396 Cost: $6,403 |
$1,870 | 46,755 | $9,526 | 310 | - | - | - | - |
$1,870 46,755 kWh |
$9,526 310 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $673 Cost: $240 |
$191 | 4,763 | $482 | 16 | - | - | - | - |
$191 4,763 kWh |
$482 16 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $20,235 Cost: $100,548 |
- | - | - | - | $10,650 | 5,000 | $9,585 | - |
- - kWh |
- - kW-months/year |
$10,650 5,000 MMBtu |
$9,585 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.6232 INSTALL SET-BACK TIMERS |
Savings: $86,283 Cost: $371,500 |
$12,800 | 320,000 | $20,233 | 658 | $53,250 | 25,000 | - | - |
$12,800 320,000 kWh |
$20,233 658 kW-months/year |
$53,250 25,000 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $3,605 Cost: - |
$1,020 | 25,505 | $2,584 | 84 | - | - | - | - |
$1,020 25,505 kWh |
$2,584 84 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $270 Cost: $189 |
$76 | 1,900 | $194 | 6 | - | - | - | - |
$76 1,900 kWh |
$194 6 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $4,201 Cost: $33,470 |
- | - | - | - | $4,201 | 1,973 | - | - |
- - kWh |
- - kW-months/year |
$4,201 1,973 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.7312 MINIMIZE USE OF OUTSIDE MAKE-UP AIR FOR VENTILATION EXCEPT WHEN USED FOR ECONOMIZER CYCLE |
Savings: $2,870 Cost: $5,510 |
- | - | - | - | $2,870 | 1,348 | - | - |
- - kWh |
- - kW-months/year |
$2,870 1,348 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
12: 2.7446 UTILIZE SENSORS CONTROLLING ROOF AND WALL OPENINGS |
Savings: $4,105 Cost: $5,076 |
- | - | - | - | $4,105 | 1,927 | - | - |
- - kWh |
- - kW-months/year |
$4,105 1,927 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $165,679 Cost: $550,582 |
$14,905 | 372,634 | $33,019 | 1,075 | $108,170 | 50,784 | $9,585 | - | $14,905 372,634 kWh |
$33,019 1,075 kW-months/year |
$108,170 50,784 MMBtu |
$9,585 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $157,264 Cost: $510,569 |
$14,829 | 370,734 | $32,826 | 1,068 | $100,024 | 46,960 | $9,585 | - | $14,829 370,734 kWh |
$32,826 1,068 kW-months/year |
$100,024 46,960 MMBtu |
$9,585 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes | Electricity Usage | Electricity Demand | Natural Gas | Administrative Changes |