Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Missouri-Columbia |
---|---|
Assessment Year | 2024 |
Principal Product | metal cans |
NAICS | 332431 - Metal Can Manufacturing |
SIC | 3411 - Metal Cans |
Sales | $100,000,000-$500,000,000 |
# of Employees | 112 |
Plant Area (Sq.Ft.) | 414,000 |
Annual Production | 1,231,711,104 Pieces |
Production Hrs. Annual | 4,368 |
Location (State) | IA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $1,232,879 | 31,813,600 | kWh | $0.04 |
Electricity Demand | $1,206,380 | 52,999 | kW-months/year | $22.76 |
Natural Gas | $742,452 | 322,266 | MMBtu | $2.30 |
TOTAL ENERGY COSTS | $3,431,146 | |||
RECOMMENDED SAVINGS* | $193,490 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Water Usage | Water Disposal | Electricity Usage | Electricity Demand | Water Usage | Water Disposal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | Tgal | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.4159 REPLACE TREATED WATER WITH WELL / SURFACE WATER |
Savings: $21,410 Cost: $168,000 |
- | - | - | - | $11,785 | 5,333 | $9,625 | 2,667 |
- - kWh |
- - kW-months/year |
$11,785 5,333 Tgal |
$9,625 2,667 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $9,395 Cost: $800 |
$3,609 | 92,542 | $5,786 | 254 | - | - | - | - |
$3,609 92,542 kWh |
$5,786 254 kW-months/year |
- - Tgal |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $3,674 Cost: $14,000 |
$3,674 | 94,198 | - | - | - | - | - | - |
$3,674 94,198 kWh |
- - kW-months/year |
- - Tgal |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $11,668 Cost: $59,968 |
$3,884 | 99,591 | $7,784 | 342 | - | - | - | - |
$3,884 99,591 kWh |
$7,784 342 kW-months/year |
- - Tgal |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $147,343 Cost: $2,297,063 |
$147,343 | 3,778,038 | - | - | - | - | - | - |
$147,343 3,778,038 kWh |
- - kW-months/year |
- - Tgal |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $193,490 Cost: $2,539,831 |
$158,510 | 4,064,369 | $13,570 | 596 | $11,785 | 5,333 | $9,625 | 2,667 | $158,510 4,064,369 kWh |
$13,570 596 kW-months/year |
$11,785 5,333 Tgal |
$9,625 2,667 Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - Tgal |
- - Tgal |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | Tgal | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Water Usage | Water Disposal | Electricity Usage | Electricity Demand | Water Usage | Water Disposal |