Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Oregon State University |
---|---|
Assessment Year | 2019 |
Principal Product | Hardwood Plywood |
NAICS | 321211 - Hardwood Veneer and Plywood Manufacturing |
SIC | 2435 - Hardwood Veneer And Plywood |
Sales | $100,000,000-$500,000,000 |
# of Employees | 230 |
Plant Area (Sq.Ft.) | 622,518 |
Annual Production | 100,000,000 Units |
Production Hrs. Annual | 6,240 |
Location (State) | OR |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $695,642 | 17,192,800 | kWh | $0.04 |
Electricity Demand | $301,449 | 38,455 | kW-months/year | $7.84 |
Electricity Fees | $(-51,548) | - | $ | - |
TOTAL ENERGY COSTS | $945,543 | |||
RECOMMENDED SAVINGS* | $70,632 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $4,008 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $29,023 Cost: $34,574 |
$20,636 | 509,540 | $8,387 | 1,019 |
$20,636 509,540 kWh |
$8,387 1,019 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4113 INSTALL MOTOR VOLTAGE CONTROLLER ON LIGHTLY LOADED MOTORS |
Savings: $29,427 Cost: $34,054 |
$13,546 | 334,472 | $15,881 | 1,930 |
$13,546 334,472 kWh |
$15,881 1,930 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $8,174 Cost: $4,152 |
$5,877 | 145,109 | $2,297 | 279 |
$5,877 145,109 kWh |
$2,297 279 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $4,008 Cost: - |
$1,728 | 42,675 | $2,280 | 277 |
$1,728 42,675 kWh |
$2,280 277 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $70,632 Cost: $72,780 |
$41,787 | 1,031,796 | $28,845 | 3,505 | $41,787 1,031,796 kWh |
$28,845 3,505 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $4,008 Cost: - |
$1,728 | 42,675 | $2,280 | 277 | $1,728 42,675 kWh |
$2,280 277 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |