Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | San Diego State University |
---|---|
Assessment Year | 2001 |
Principal Product | Aluminum forgings for aerospace |
NAICS | n/a |
SIC | 3463 - Nonferrous Forgings |
Sales | $10,000,000-$50,000,000 |
# of Employees | 185 |
Plant Area (Sq.Ft.) | 150,000 |
Annual Production | 1,500,000 Pounds |
Production Hrs. Annual | 4,725 |
Location (State) | CA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $347,790 | 5,253,011 | kWh | $0.07 |
Electricity Demand | $174,280 | 18,770 | kW-months/year | $9.29 |
Electricity Fees | $7,896 | - | $ | - |
Natural Gas | $332,900 | 66,651 | MMBtu | $4.99 |
TOTAL ENERGY COSTS | $870,972 | |||
RECOMMENDED SAVINGS* | $1,607,000 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $89,479 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $22,159 Cost: $5,200 |
$16,334 | 246,739 | $5,825 | 627 | - | - | - | - | - | - | - | - |
$16,334 246,739 kWh |
$5,825 627 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4323 USE OPTIMUM SIZE AND CAPACITY EQUIPMENT |
Savings: $24,052 Cost: $18,000 |
- | - | - | - | $24,052 | 4,961 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$24,052 4,961 MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $54,857 Cost: $120,000 |
$49,562 | 748,678 | $5,295 | 570 | - | - | - | - | - | - | - | - |
$49,562 748,678 kWh |
$5,295 570 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $5,213 Cost: $400 |
$3,843 | 58,054 | $1,370 | 147 | - | - | - | - | - | - | - | - |
$3,843 58,054 kWh |
$1,370 147 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $5,172 Cost: $7,600 |
$3,813 | 57,592 | $1,359 | 146 | - | - | - | - | - | - | - | - |
$3,813 57,592 kWh |
$1,359 146 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $2,078 Cost: $2,000 |
- | - | - | - | $2,078 | 429 | - | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$2,078 429 MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4322 USE OR REPLACE WITH ENERGY EFFICIENT SUBSTITUTES |
Savings: $1,318 Cost: $2,550 |
$653 | 9,870 | $665 | 72 | - | - | - | - | - | - | - | - |
$653 9,870 kWh |
$665 72 kW-months/year |
- - MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT |
Savings: $1,288,713 Cost: $1,830,400 |
$402,254 | 6,076,350 | $143,363 | 15,432 | $424,695 | 87,602 | - | - | - | - | $318,401 | - |
$402,254 6,076,350 kWh |
$143,363 15,432 kW-months/year |
$424,695 87,602 MMBtu |
- - $ |
- - $ |
$318,401 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS |
Savings: $6,638 Cost: $15,000 |
- | - | - | - | - | - | - | - | - | - | $6,638 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
- - $ |
$6,638 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 4.446 AUTOMATE FINISHING PROCESS |
Savings: $196,800 Cost: $56,000 |
- | - | - | - | - | - | $211,800 | - | $(-15,000) | - | - | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$211,800 - $ |
$(-15,000) - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $1,607,000 Cost: $2,057,150 |
$476,459 | 7,197,283 | $157,877 | 16,994 | $450,825 | 92,992 | $211,800 | - | $(-15,000) | - | $325,039 | - | $476,459 7,197,283 kWh |
$157,877 16,994 kW-months/year |
$450,825 92,992 MMBtu |
$211,800 - $ |
$(-15,000) - $ |
$325,039 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $89,479 Cost: $135,200 |
$73,552 | 1,111,063 | $13,849 | 1,490 | $2,078 | 429 | - | - | - | - | - | - | $73,552 1,111,063 kWh |
$13,849 1,490 kW-months/year |
$2,078 429 MMBtu |
- - $ |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Natural Gas | Personnel Changes | Administrative Changes | One-time Revenue or Avoided Cost |