Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Diego State University
Assessment Year 2003
Principal Product Seals
NAICS 339991 - Gasket, Packing, and Sealing Device Manufacturing
SIC 3053 - Gaskets, Packing And Sealing Devices
Sales $50,000,000-$100,000,000
# of Employees 120
Plant Area (Sq.Ft.) 70,000
Annual Production 5,000,000 Pieces
Production Hrs. Annual 6,000
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $172,680 2,068,411 kWh $0.08
Electricity Demand $58,992 5,253 kW-months/year $11.23
TOTAL ENERGY COSTS $236,672
RECOMMENDED SAVINGS* $99,263 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $10,234
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Solid Waste (non-haz) Electricity Usage Electricity Demand Solid Waste (non-haz)
$ kWh $ kW-months/year $ lb
01: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$74,855
Cost:
$44,000
$63,063 735,000 $11,792 1,050 - - $63,063
735,000
kWh
$11,792
1,050
kW-months/year
-
-
lb
02: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$10,234
Cost:
-
$10,234 119,280 - - - - $10,234
119,280
kWh
-
-
kW-months/year
-
-
lb
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE Savings:
$4,011
Cost:
$2,300
$541 6,303 $3,470 309 - - $541
6,303
kWh
$3,470
309
kW-months/year
-
-
lb
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$2,845
Cost:
-
$2,250 26,229 $595 53 - - $2,250
26,229
kWh
$595
53
kW-months/year
-
-
lb
05: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$2,842
Cost:
$5,400
$2,763 32,198 $79 7 - - $2,763
32,198
kWh
$79
7
kW-months/year
-
-
lb
06: 2.7134 USE PHOTOCELL CONTROLS Savings:
$1,476
Cost:
$582
$721 8,400 $755 67 - - $721
8,400
kWh
$755
67
kW-months/year
-
-
lb
07: 3.6193 INSTALL EQUIPMENT (eg COMPACTOR) TO REDUCE DISPOSAL COSTS Savings:
$3,000
Cost:
$5,000
- - - - $3,000 - -
-
kWh
-
-
kW-months/year
$3,000
-
lb
TOTAL RECOMMENDED Savings:
$99,263
Cost:
$57,282
$79,572 927,410 $16,691 1,486 $3,000 - $79,572
927,410
kWh
$16,691
1,486
kW-months/year
$3,000
-
lb
TOTAL IMPLEMENTED Savings:
$10,234
Cost:
-
$10,234 119,280 - - - - $10,234
119,280
kWh
-
-
kW-months/year
-
-
lb
Savings
Cost
$ kWh $ kW-months/year $ lb
Electricity Usage Electricity Demand Solid Waste (non-haz) Electricity Usage Electricity Demand Solid Waste (non-haz)