Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Diego State University
Assessment Year 2011
Principal Product Sheet Metal HVAC Duct
NAICS 332322 - Sheet Metal Work Manufacturing
SIC 3444 - Sheet Metalwork
Sales $10,000,000-$50,000,000
# of Employees 80
Plant Area (Sq.Ft.) 70,000
Annual Production 456,000 Pounds
Production Hrs. Annual 3,570
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $48,109 473,892 kWh $0.10
Electricity Demand $12,009 1,427 kW-months/year $8.42
TOTAL ENERGY COSTS $60,118
RECOMMENDED SAVINGS* $6,715 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $1,286
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Usage Electricity Demand
$ kWh $ kW-months/year
01: 2.7121 UTILIZE DAYLIGHT WHENEVER POSSIBLE IN LIEU OF ARTIFICIAL LIGHT Savings:
$213
Cost:
-
$213 2,097 - - $213
2,097
kWh
-
-
kW-months/year
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$1,286
Cost:
$500
$834 8,218 $452 54 $834
8,218
kWh
$452
54
kW-months/year
03: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$89
Cost:
$98
$89 881 - - $89
881
kWh
-
-
kW-months/year
04: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$817
Cost:
$2,000
$817 8,051 - - $817
8,051
kWh
-
-
kW-months/year
05: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD Savings:
$4,310
Cost:
$10,000
$4,310 42,467 - - $4,310
42,467
kWh
-
-
kW-months/year
TOTAL RECOMMENDED Savings:
$6,715
Cost:
$12,598
$6,263 61,714 $452 54 $6,263
61,714
kWh
$452
54
kW-months/year
TOTAL IMPLEMENTED Savings:
$1,286
Cost:
$500
$834 8,218 $452 54 $834
8,218
kWh
$452
54
kW-months/year
Savings
Cost
$ kWh $ kW-months/year
Electricity Usage Electricity Demand Electricity Usage Electricity Demand