IAC logo
IAC Assessment: SD0446
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: SD0446
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Diego State University
Assessment Year 2012
Principal Product Acoustic and Electric Guitars
NAICS 425120 - Wholesale Trade Agents and Brokers
SIC 5099 - Durable Goods, Nec
Sales $50,000,000-$100,000,000
# of Employees 450
Plant Area (Sq.Ft.) 65,000
Annual Production 100,000 Pieces
Production Hrs. Annual 5,880
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $257,461 2,951,611 kWh $0.09
Electricity Demand $182,088 8,218 kW-months/year $22.16
Electricity Fees $1,763 - $ -
Natural Gas $34,544 4,325 MMBtu $7.99
TOTAL ENERGY COSTS $475,856
RECOMMENDED SAVINGS* $34,745 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $30,961
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$629
Cost:
$100
$629 7,208 - - - - $629
7,208
kWh
-
-
kW-months/year
-
-
MMBtu
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,854
Cost:
$500
$2,538 29,110 $1,316 59 - - $2,538
29,110
kWh
$1,316
59
kW-months/year
-
-
MMBtu
03: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$11,000
Cost:
$4,045
- - - - $11,000 1,315 -
-
kWh
-
-
kW-months/year
$11,000
1,315
MMBtu
04: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$15,478
Cost:
$15,745
$10,193 116,891 $5,285 239 - - $10,193
116,891
kWh
$5,285
239
kW-months/year
-
-
MMBtu
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$2,589
Cost:
$3,425
$2,589 29,691 - - - - $2,589
29,691
kWh
-
-
kW-months/year
-
-
MMBtu
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$1,195
Cost:
$3,425
$1,195 13,704 - - - - $1,195
13,704
kWh
-
-
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$34,745
Cost:
$27,240
$17,144 196,604 $6,601 298 $11,000 1,315 $17,144
196,604
kWh
$6,601
298
kW-months/year
$11,000
1,315
MMBtu
TOTAL IMPLEMENTED Savings:
$30,961
Cost:
$20,390
$13,360 153,209 $6,601 298 $11,000 1,315 $13,360
153,209
kWh
$6,601
298
kW-months/year
$11,000
1,315
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas