Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Diego State University
Assessment Year 2015
Principal Product Corrugated Paper
NAICS 322211 - Corrugated and Solid Fiber Box Manufacturing
SIC 2653 - Corrugated And Solid Fiber Boxes
Sales >$500,000,000
# of Employees 75
Plant Area (Sq.Ft.) 241,850
Annual Production 2,000,000,000 Pieces
Production Hrs. Annual 7,488
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $811,839 10,769,328 kWh $0.08
Electricity Demand $400,466 15,720 kW-months/year $25.47
Electricity Fees $142,722 - $ -
Natural Gas $446,260 68,848 MMBtu $6.48
TOTAL ENERGY COSTS $1,801,287
RECOMMENDED SAVINGS* $120,505 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $62,640
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$55,666
Cost:
$90,550
- - - - $55,666 8,591 -
-
kWh
-
-
kW-months/year
$55,666
8,591
MMBtu
02: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$47,366
Cost:
$73,800
$30,506 404,563 $16,860 662 - - $30,506
404,563
kWh
$16,860
662
kW-months/year
-
-
MMBtu
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS Savings:
$11,773
Cost:
$3,400
$11,773 268,173 - - - - $11,773
268,173
kWh
-
-
kW-months/year
-
-
MMBtu
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$3,501
Cost:
$800
$3,501 46,426 - - - - $3,501
46,426
kWh
-
-
kW-months/year
-
-
MMBtu
05: 2.2614 USE COOLING TOWER OR ECONOMIZER TO REPLACE CHILLER COOLING Savings:
$2,199
Cost:
$2,199
$1,083 14,363 $1,116 44 - - $1,083
14,363
kWh
$1,116
44
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$120,505
Cost:
$170,749
$46,863 733,525 $17,976 706 $55,666 8,591 $46,863
733,525
kWh
$17,976
706
kW-months/year
$55,666
8,591
MMBtu
TOTAL IMPLEMENTED Savings:
$62,640
Cost:
$78,000
$45,780 719,162 $16,860 662 - - $45,780
719,162
kWh
$16,860
662
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas