IAC logo
IAC Assessment: SF0538
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: SF0538
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center San Francisco State University
Assessment Year 2019
Principal Product almonds
NAICS 311911 - Roasted Nuts and Peanut Butter Manufacturing
SIC 2068 - Salted And Roasted Nuts And Seeds
Sales $50,000,000-$100,000,000
# of Employees 241
Plant Area (Sq.Ft.) 290,000
Annual Production 60,000,000 Pounds
Production Hrs. Annual 8,760
Location (State) CA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,053,168 11,549,814 kWh $0.09
Electricity Demand $364,677 23,952 kW-months/year $15.23
Natural Gas $204,568 25,704 MMBtu $7.96
TOTAL ENERGY COSTS $1,622,413
RECOMMENDED SAVINGS* $508,453 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $96,672
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees Natural Gas Electricity Usage Electricity Demand Electricity Fees Natural Gas
$ kWh $ kW-months/year $ $ $ MMBtu
01: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE Savings:
$146,044
Cost:
-
- - - - $146,044 - - - -
-
kWh
-
-
kW-months/year
$146,044
-
$
-
-
MMBtu
02: 2.2621 MODIFY REFRIGERATION SYSTEM TO OPERATE AT A LOWER PRESSURE Savings:
$29,680
Cost:
$12,500
$29,680 325,507 - - - - - - $29,680
325,507
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
03: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS Savings:
$15,353
Cost:
$5,947
$5,196 56,988 - - - - $10,157 1,277 $5,196
56,988
kWh
-
-
kW-months/year
-
-
$
$10,157
1,277
MMBtu
04: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER Savings:
$27,526
Cost:
$16,915
$31,896 349,814 $7,293 480 - - $(-11,663) (-1,466) $31,896
349,814
kWh
$7,293
480
kW-months/year
-
-
$
$(-11,663)
(-1,466)
MMBtu
05: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$11,440
Cost:
$7,616
$11,440 125,465 - - - - - - $11,440
125,465
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$8,101
Cost:
$5,998
$8,101 88,849 - - - - - - $8,101
88,849
kWh
-
-
kW-months/year
-
-
$
-
-
MMBtu
07: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$25,533
Cost:
$34,367
$20,781 227,915 $4,752 312 - - - - $20,781
227,915
kWh
$4,752
312
kW-months/year
-
-
$
-
-
MMBtu
08: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$6,565
Cost:
$11,649
$5,343 58,601 $1,222 80 - - - - $5,343
58,601
kWh
$1,222
80
kW-months/year
-
-
$
-
-
MMBtu
09: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$238,211
Cost:
$1,672,972
$219,812 2,410,750 $18,399 1,188 - - - - $219,812
2,410,750
kWh
$18,399
1,188
kW-months/year
-
-
$
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$508,453
Cost:
$1,767,964
$332,249 3,643,889 $31,666 2,060 $146,044 - $(-1,506) (-189) $332,249
3,643,889
kWh
$31,666
2,060
kW-months/year
$146,044
-
$
$(-1,506)
(-189)
MMBtu
TOTAL IMPLEMENTED Savings:
$96,672
Cost:
$78,077
$80,541 883,325 $5,974 392 - - $10,157 1,277 $80,541
883,325
kWh
$5,974
392
kW-months/year
-
-
$
$10,157
1,277
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ $ $ MMBtu
Electricity Usage Electricity Demand Electricity Fees Natural Gas Electricity Usage Electricity Demand Electricity Fees Natural Gas