Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2001 |
Principal Product | webbing straps |
NAICS | n/a |
SIC | 2241 - Narrow Fabric Mills |
Sales | $100,000,000-$500,000,000 |
# of Employees | 84 |
Plant Area (Sq.Ft.) | 62,000 |
Annual Production | 0 Units |
Production Hrs. Annual | 2,040 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $49,620 | 837,626 | kWh | $0.06 |
Electricity Demand | $18,981 | 2,329 | kW-months/year | $8.15 |
Electricity Fees | $1,169 | - | $ | - |
Natural Gas | $26,192 | 4,008 | MMBtu | $6.53 |
TOTAL ENERGY COSTS | $95,962 | |||
RECOMMENDED SAVINGS* | $19,575 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $13,706 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 4.511 EXPAND OPERATIONS INTO UNUSED SPACE |
Savings: $3,042 Cost: $30 |
$1,362 | 6,656 | - | - | $1,680 | 209 |
$1,362 6,656 kWh |
- - kW-months/year |
$1,680 209 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $319 Cost: - |
$319 | 4,559 | - | - | - | - |
$319 4,559 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $2,827 Cost: $2,088 |
- | - | - | - | $2,827 | 467 |
- - kWh |
- - kW-months/year |
$2,827 467 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $2,183 Cost: $90 |
$1,295 | 18,505 | $888 | 9 | - | - |
$1,295 18,505 kWh |
$888 9 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS |
Savings: $421 Cost: - |
$421 | 6,021 | - | - | - | - |
$421 6,021 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS |
Savings: $10,560 Cost: $120,000 |
- | - | - | - | $10,560 | 1,743 |
- - kWh |
- - kW-months/year |
$10,560 1,743 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7243 IMPROVE AIR CIRCULATION WITH DESTRATIFICATION FANS / OTHER METHODS |
Savings: $223 Cost: - |
$223 | 3,196 | - | - | - | - |
$223 3,196 kWh |
- - kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $19,575 Cost: $122,208 |
$3,620 | 38,937 | $888 | 9 | $15,067 | 2,419 | $3,620 38,937 kWh |
$888 9 kW-months/year |
$15,067 2,419 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $13,706 Cost: $122,088 |
$319 | 4,559 | - | - | $13,387 | 2,210 | $319 4,559 kWh |
- - kW-months/year |
$13,387 2,210 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |