Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2002 |
Principal Product | Brake controls and related components for railroad freight cars |
NAICS | n/a |
SIC | 3743 - Railroad Equipment |
Sales | $50,000,000-$100,000,000 |
# of Employees | 261 |
Plant Area (Sq.Ft.) | 258,000 |
Annual Production | 12,400 Pieces |
Production Hrs. Annual | 3,840 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $481,747 | 6,395,540 | kWh | $0.08 |
Electricity Demand | $79,229 | 14,458 | kW-months/year | $5.48 |
Electricity Fees | $8,470 | - | $ | - |
Natural Gas | $262,636 | 32,985 | MMBtu | $7.96 |
TOTAL ENERGY COSTS | $865,366 | |||
RECOMMENDED SAVINGS* | $48,610 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $13,161 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Consumption | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Consumption | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | Tgal | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES |
Savings: $14,024 Cost: $6,613 |
- | - | - | - | - | - | $14,024 | 1,998 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$14,024 1,998 MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $11,420 Cost: $89 |
$11,420 | 163,142 | - | - | - | - | - | - | - | - |
$11,420 163,142 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $8,470 Cost: $23,250 |
- | - | - | - | $8,470 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$8,470 - $ |
- - MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $4,103 Cost: $178 |
- | - | - | - | - | - | $4,103 | 584 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$4,103 584 MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $4,031 Cost: $706 |
$2,707 | 38,667 | $1,324 | 20 | - | - | - | - | - | - |
$2,707 38,667 kWh |
$1,324 20 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.2514 COVER OPEN TANKS |
Savings: $2,938 Cost: $1,769 |
- | - | - | - | - | - | $2,938 | 419 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$2,938 419 MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,453 Cost: $299 |
$1,134 | 16,195 | $319 | 5 | - | - | - | - | - | - |
$1,134 16,195 kWh |
$319 5 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS |
Savings: $1,197 Cost: $22 |
- | - | - | - | - | - | $614 | 87 | $583 | - |
- - kWh |
- - kW-months/year |
- - $ |
$614 87 MMBtu |
$583 - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $686 Cost: $1,106 |
- | - | - | - | - | - | $686 | 98 | - | - |
- - kWh |
- - kW-months/year |
- - $ |
$686 98 MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $288 Cost: - |
$231 | 3,302 | $57 | 1 | - | - | - | - | - | - |
$231 3,302 kWh |
$57 1 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $48,610 Cost: $34,032 |
$15,492 | 221,306 | $1,700 | 26 | $8,470 | - | $22,365 | 3,186 | $583 | - | $15,492 221,306 kWh |
$1,700 26 kW-months/year |
$8,470 - $ |
$22,365 3,186 MMBtu |
$583 - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $13,161 Cost: $388 |
$12,785 | 182,639 | $376 | 6 | - | - | - | - | - | - | $12,785 182,639 kWh |
$376 6 kW-months/year |
- - $ |
- - MMBtu |
- - Tgal |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | $ | Tgal | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Consumption | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Water Consumption |