Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Syracuse University |
---|---|
Assessment Year | 2003 |
Principal Product | Corrugated shipping containers |
NAICS | 322211 - Corrugated and Solid Fiber Box Manufacturing |
SIC | 2510 - |
Sales | $10,000,000-$50,000,000 |
# of Employees | 120 |
Plant Area (Sq.Ft.) | 160,000 |
Annual Production | 420,000,000 Thousand Feet |
Production Hrs. Annual | 4,160 |
Location (State) | NY |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $192,674 | 2,637,000 | kWh | $0.07 |
Electricity Demand | $112,858 | 7,539 | kW-months/year | $14.97 |
Electricity Fees | $1,661 | - | $ | - |
Natural Gas | $153,054 | 36,214 | MMBtu | $4.23 |
TOTAL ENERGY COSTS | $466,636 | |||
RECOMMENDED SAVINGS* | $13,478 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $827 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $7,229 Cost: $6,100 |
- | - | - | - | - | - | $7,229 | 1,709 |
- - kWh |
- - kW-months/year |
- - $ |
$7,229 1,709 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $2,655 Cost: $2,035 |
$1,518 | 21,696 | $1,137 | 76 | - | - | - | - |
$1,518 21,696 kWh |
$1,137 76 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $1,138 Cost: $5,410 |
- | - | - | - | $1,138 | - | - | - |
- - kWh |
- - kW-months/year |
$1,138 - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $1,003 Cost: $1,065 |
$1,003 | 70,512 | - | - | - | - | - | - |
$1,003 70,512 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $720 Cost: $133 |
$720 | 10,285 | - | - | - | - | - | - |
$720 10,285 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $376 Cost: - |
$376 | 5,370 | - | - | - | - | - | - |
$376 5,370 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $250 Cost: $1,031 |
$250 | 3,571 | - | - | - | - | - | - |
$250 3,571 kWh |
- - kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $107 Cost: - |
$102 | 1,456 | $5 | 1 | - | - | - | - |
$102 1,456 kWh |
$5 1 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $13,478 Cost: $15,774 |
$3,969 | 112,890 | $1,142 | 77 | $1,138 | - | $7,229 | 1,709 | $3,969 112,890 kWh |
$1,142 77 kW-months/year |
$1,138 - $ |
$7,229 1,709 MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $827 Cost: $133 |
$822 | 11,741 | $5 | 1 | - | - | - | - | $822 11,741 kWh |
$5 1 kW-months/year |
- - $ |
- - MMBtu |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas | Electricity Usage | Electricity Demand | Electricity Fees | Natural Gas |