Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Tennessee |
---|---|
Assessment Year | 1998 |
Principal Product | Chopped Fiber Glass |
NAICS | n/a |
SIC | 3229 - Pressed And Blown Glass, Nec |
Sales | $50,000,000-$100,000,000 |
# of Employees | 230 |
Plant Area (Sq.Ft.) | 362,000 |
Annual Production | 120,000,000 Pounds |
Production Hrs. Annual | 8,760 |
Location (State) | TN |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $3,354,612 | 140,894,492 | kWh | $0.02 |
Electricity Demand | $1,117,834 | 206,581 | kW-months/year | $5.41 |
Electricity Fees | $(-25,036) | - | $ | - |
Natural Gas | $2,034,184 | 685,461 | MMBtu | $2.97 |
TOTAL ENERGY COSTS | $6,850,934 | |||
RECOMMENDED SAVINGS* | $608,611 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $5,830 |
#|Description |
Savings Cost |
Status | Electricity Usage | Other Liquid (haz) | Solid Waste (non-haz) | Administrative Changes | By-product Production | Electricity Usage | Other Liquid (haz) | Solid Waste (non-haz) | Administrative Changes | By-product Production | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | gal | $ | lb | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.5313 INCREASE AMOUNT OF WASTE RECOVERED FOR RESALE |
Savings: $494,000 Cost: $32,000 |
- | - | - | - | $190,000 | - | - | - | $304,000 | - |
- - kWh |
- - gal |
$190,000 - lb |
- - $ |
$304,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 3.3128 UTILIZE OTHER METHODS TO REMOVE CONTAMINANTS |
Savings: $89,750 Cost: $45,600 |
- | - | $89,750 | - | - | - | - | - | - | - |
- - kWh |
$89,750 - gal |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 4.431 TRAIN OPERATORS FOR MAXIMUM OPERATING EFFICIENCY |
Savings: $7,500 Cost: $5,600 |
- | - | - | - | - | - | $7,500 | - | - | - |
- - kWh |
- - gal |
- - lb |
$7,500 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7131 ADD AREA LIGHTING SWITCHES |
Savings: $6,606 Cost: $10,900 |
$6,606 | 235,932 | - | - | - | - | - | - | - | - |
$6,606 235,932 kWh |
- - gal |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $5,830 Cost: $7,750 |
$5,830 | 208,089 | - | - | - | - | - | - | - | - |
$5,830 208,089 kWh |
- - gal |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $4,925 Cost: $4,725 |
$4,925 | 175,850 | - | - | - | - | - | - | - | - |
$4,925 175,850 kWh |
- - gal |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $608,611 Cost: $106,575 |
$17,361 | 619,871 | $89,750 | - | $190,000 | - | $7,500 | - | $304,000 | - | $17,361 619,871 kWh |
$89,750 - gal |
$190,000 - lb |
$7,500 - $ |
$304,000 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $5,830 Cost: $7,750 |
$5,830 | 208,089 | - | - | - | - | - | - | - | - | $5,830 208,089 kWh |
- - gal |
- - lb |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | gal | $ | lb | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||