IAC logo
IAC Assessment: TT0098
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: TT0098
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Tennessee Technological University
Assessment Year 2012
Principal Product Motor Vehicle Parts And Accessories
NAICS 336390 - Other Motor Vehicle Parts Manufacturing
SIC 3714 - Motor Vehicle Parts And Accessories
Sales $10,000,000-$50,000,000
# of Employees 100
Plant Area (Sq.Ft.) 100,000
Annual Production 0 Units
Production Hrs. Annual 1,500
Location (State) TN
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $191,648 3,066,600 kWh $0.06
Electricity Demand $71,437 6,815 kW-months/year $10.48
Natural Gas $10,013 1,182 MMBtu $8.47
TOTAL ENERGY COSTS $281,614
RECOMMENDED SAVINGS* $17,368 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $9,656
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.7226 USE COMPUTER PROGRAMS TO OPTIMIZE HVAC PERFORMANCE Savings:
$1,053
Cost:
$1,116
$873 10,040 - - $179 21 $873
10,040
kWh
-
-
kW-months/year
$179
21
MMBtu
02: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$1,222
Cost:
$2,320
$1,222 19,270 - - - - $1,222
19,270
kWh
-
-
kW-months/year
-
-
MMBtu
03: 2.3512 DE-ENERGIZE EXCESS TRANSFORMER CAPACITY Savings:
$1,898
Cost:
$5,525
$1,898 30,613 - - - - $1,898
30,613
kWh
-
-
kW-months/year
-
-
MMBtu
04: 2.9111 USE SOLAR HEAT TO HEAT MAKE-UP AIR Savings:
$5,814
Cost:
$43,695
- - - - $5,814 473 -
-
kWh
-
-
kW-months/year
$5,814
473
MMBtu
05: 2.2135 REPAIR AND ELIMINATE STEAM LEAKS Savings:
$7,381
Cost:
$980
$3,721 41,804 $3,660 347 - - $3,721
41,804
kWh
$3,660
347
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$17,368
Cost:
$53,636
$7,715 101,728 $3,660 347 $5,993 494 $7,715
101,728
kWh
$3,660
347
kW-months/year
$5,993
494
MMBtu
TOTAL IMPLEMENTED Savings:
$9,656
Cost:
$4,416
$5,816 71,114 $3,660 347 $179 21 $5,816
71,114
kWh
$3,660
347
kW-months/year
$179
21
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu
Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas