IAC Center | Tennessee Technological University |
---|---|
Assessment Year | 2019 |
Principal Product | Jackets and Bibs |
NAICS | 315220 - Men’s and Boys’ Cut and Sew Apparel Manufacturing |
SIC | 2326 - Men's and Boys' Work Clothing |
Sales | $50,000,000-$100,000,000 |
# of Employees | 196 |
Plant Area (Sq.Ft.) | 78,000 |
Annual Production | 370,673 Units |
Production Hrs. Annual | 2,100 |
Location (State) | TN |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $73,367 | 1,029,120 | kWh | $0.07 |
Electricity Demand | $52,762 | 4,956 | kW-months/year | $10.65 |
Natural Gas | $8,102 | 812 | MMBtu | $9.98 |
TOTAL ENERGY COSTS | $135,944 | |||
RECOMMENDED SAVINGS* | $17,320 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $15,882 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $7,113 Cost: $17,840 |
$7,113 | 99,762 | - | - |
$7,113 99,762 kWh |
- - kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $5,538 Cost: $4,300 |
$4,235 | 59,404 | $1,303 | 122 |
$4,235 59,404 kWh |
$1,303 122 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $1,880 Cost: $100 |
$1,880 | 26,368 | - | - |
$1,880 26,368 kWh |
- - kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7231 USE RADIANT HEATER FOR SPOT HEATING |
Savings: $1,438 Cost: $1,100 |
$1,438 | 20,168 | - | - |
$1,438 20,168 kWh |
- - kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $1,351 Cost: $1,100 |
$1,351 | 18,953 | - | - |
$1,351 18,953 kWh |
- - kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $17,320 Cost: $24,440 |
$16,017 | 224,655 | $1,303 | 122 | $16,017 224,655 kWh |
$1,303 122 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $15,882 Cost: $23,340 |
$14,579 | 204,487 | $1,303 | 122 | $14,579 204,487 kWh |
$1,303 122 kW-months/year |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Usage | Electricity Demand |