Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Tennessee Technological University |
---|---|
Assessment Year | 2021 |
Principal Product | Wire and Cable |
NAICS | 335921 - Fiber Optic Cable Manufacturing |
SIC | 3357 - Nonferrous Wiredrawing & Insulating |
Sales | $50,000,000-$100,000,000 |
# of Employees | 109 |
Plant Area (Sq.Ft.) | 182,859 |
Annual Production | 421,000 Thousand Feet |
Production Hrs. Annual | 6,000 |
Location (State) | TN |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $626,303 | 10,069,880 | kWh | $0.06 |
Electricity Demand | $241,357 | 21,268 | kW-months/year | $11.35 |
Natural Gas | $9,812 | 1,328 | MMBtu | $7.39 |
TOTAL ENERGY COSTS | $900,092 | |||
RECOMMENDED SAVINGS* | $319,413 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $269,726 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Ancillary Material Cost | Electricity Usage | Electricity Demand | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7425 CLEAN OR COLOR ROOF TO REDUCE SOLAR LOAD |
Savings: $188,912 Cost: $733,702 |
$51,499 | 827,960 | $269 | 24 | $137,144 | - |
$51,499 827,960 kWh |
$269 24 kW-months/year |
$137,144 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $49,358 Cost: $3,200 |
$36,163 | 581,400 | $13,195 | 1,163 | - | - |
$36,163 581,400 kWh |
$13,195 1,163 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7241 INSTALL OUTSIDE AIR DAMPER / ECONOMIZER ON HVAC UNIT |
Savings: $30,912 Cost: $38,200 |
$30,912 | 496,973 | - | - | - | - |
$30,912 496,973 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE |
Savings: $26,082 Cost: $700 |
$26,082 | 419,328 | - | - | - | - |
$26,082 419,328 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $9,133 Cost: $3,000 |
$8,669 | 139,370 | $464 | 41 | - | - |
$8,669 139,370 kWh |
$464 41 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS |
Savings: $6,718 Cost: $15,000 |
$6,718 | 108,006 | - | - | - | - |
$6,718 108,006 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $5,374 Cost: - |
$4,250 | 68,550 | $1,124 | 99 | - | - |
$4,250 68,550 kWh |
$1,124 99 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7224 REDUCE SPACE CONDITIONING DURING NON-WORKING HOURS |
Savings: $2,221 Cost: $9,600 |
$2,221 | 35,703 | - | - | - | - |
$2,221 35,703 kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $703 Cost: $850 |
$515 | 8,280 | $188 | 17 | - | - |
$515 8,280 kWh |
$188 17 kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $319,413 Cost: $804,252 |
$167,029 | 2,685,570 | $15,240 | 1,343 | $137,144 | - | $167,029 2,685,570 kWh |
$15,240 1,343 kW-months/year |
$137,144 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $269,726 Cost: $737,602 |
$117,994 | 1,897,238 | $14,588 | 1,286 | $137,144 | - | $117,994 1,897,238 kWh |
$14,588 1,286 kW-months/year |
$137,144 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Ancillary Material Cost | Electricity Usage | Electricity Demand | Ancillary Material Cost |