Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Alabama |
---|---|
Assessment Year | 2025 |
Principal Product | Wood Kitchen Cabinet |
NAICS | 337110 - Wood Kitchen Cabinet and Countertop Manufacturing |
SIC | 2434 - Wood Kitchen Cabinets |
Sales | $100,000,000-$500,000,000 |
# of Employees | 196 |
Plant Area (Sq.Ft.) | 152,000 |
Annual Production | 338,000 Units |
Production Hrs. Annual | 4,100 |
Location (State) | AL |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $236,520 | 3,134,978 | kWh | $0.08 |
Electricity Demand | $158,934 | 11,911 | kW-months/year | $13.34 |
Electricity Fees | $14,046 | - | $ | - |
Natural Gas | $85,744 | 70,319 | MMBtu | $1.22 |
TOTAL ENERGY COSTS | $495,244 | |||
RECOMMENDED SAVINGS* | $239,817 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY |
Savings: $165,904 Cost: $2,630,520 |
$154,636 | 2,050,874 | $5,580 | 418 | $5,688 | - |
$154,636 2,050,874 kWh |
$5,580 418 kW-months/year |
$5,688 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $38,546 Cost: $5,696 |
- | - | - | - | $38,546 | - |
- - kWh |
- - kW-months/year |
$38,546 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $15,160 Cost: $28,210 |
$7,638 | 101,300 | $7,002 | 525 | $520 | - |
$7,638 101,300 kWh |
$7,002 525 kW-months/year |
$520 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $3,778 Cost: $7,744 |
$2,399 | 31,816 | $1,249 | 94 | $130 | - |
$2,399 31,816 kWh |
$1,249 94 kW-months/year |
$130 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,389 Cost: $670 |
$1,528 | 20,267 | $1,745 | 131 | $116 | - |
$1,528 20,267 kWh |
$1,745 131 kW-months/year |
$116 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $10,275 Cost: $16,734 |
$6,299 | 83,548 | $3,624 | 272 | $352 | - |
$6,299 83,548 kWh |
$3,624 272 kW-months/year |
$352 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $2,765 Cost: $316 |
$2,670 | 35,417 | - | - | $95 | - |
$2,670 35,417 kWh |
- - kW-months/year |
$95 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $239,817 Cost: $2,689,890 |
$175,170 | 2,323,222 | $19,200 | 1,440 | $45,447 | - | $175,170 2,323,222 kWh |
$19,200 1,440 kW-months/year |
$45,447 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Electricity Usage | Electricity Demand | Electricity Fees |