Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Connecticut
Assessment Year 2022
Principal Product Static metal seals
NAICS 335999 - All Other Miscellaneous Electrical Equipment and Component Manufacturing
SIC 3699 - Electrical Equipment & Supplies, Nec
Sales $10,000,000-$50,000,000
# of Employees 171
Plant Area (Sq.Ft.) 55,000
Annual Production 100,000 Units
Production Hrs. Annual 8,760
Location (State) CT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $354,633 3,174,060 kWh $0.11
Electricity Demand $265,876 16,023 kW-months/year $16.59
Electricity Fees $5,004 - $ -
Natural Gas $62,305 6,779 MMBtu $9.19
TOTAL ENERGY COSTS $687,818
RECOMMENDED SAVINGS* $166,178 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $30,768
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Administrative Changes Electricity Usage Electricity Demand Administrative Changes
$ kWh $ kW-months/year $ $
01: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL Savings:
$21,740
Cost:
$114,471
$7,891 70,645 $738 45 $13,111 - $7,891
70,645
kWh
$738
45
kW-months/year
$13,111
-
$
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$7,684
Cost:
$2,000
$6,257 56,016 $1,427 86 - - $6,257
56,016
kWh
$1,427
86
kW-months/year
-
-
$
03: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$322
Cost:
$960
$264 2,359 $58 4 - - $264
2,359
kWh
$58
4
kW-months/year
-
-
$
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,344
Cost:
$200
$1,109 9,930 $234 14 - - $1,109
9,930
kWh
$234
14
kW-months/year
-
-
$
05: 2.9114 USE SOLAR HEAT TO MAKE ELECTRICTY Savings:
$135,088
Cost:
$543,322
$100,274 897,704 $46,198 2,784 $(-11,383) - $100,274
897,704
kWh
$46,198
2,784
kW-months/year
$(-11,383)
-
$
TOTAL RECOMMENDED Savings:
$166,178
Cost:
$660,953
$115,794 1,036,654 $48,655 2,932 $1,728 - $115,794
1,036,654
kWh
$48,655
2,932
kW-months/year
$1,728
-
$
TOTAL IMPLEMENTED Savings:
$30,768
Cost:
$116,671
$15,257 136,591 $2,400 145 $13,111 - $15,257
136,591
kWh
$2,400
145
kW-months/year
$13,111
-
$
Savings
Cost
$ kWh $ kW-months/year $ $
Electricity Usage Electricity Demand Administrative Changes Electricity Usage Electricity Demand Administrative Changes