Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Connecticut |
---|---|
Assessment Year | 2024 |
Principal Product | Electric Lighting Fixtures |
NAICS | 335122 - Commercial, Industrial, and Institutional Electric Lighting Fixture Manufacturing |
SIC | 3646 - Commercial Lighting Fixtures |
Sales | $10,000,000-$50,000,000 |
# of Employees | 107 |
Plant Area (Sq.Ft.) | 155,000 |
Annual Production | 100,000 Pieces |
Production Hrs. Annual | 2,125 |
Location (State) | CT |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $64,272 | 438,861 | kWh | $0.15 |
Electricity Demand | $60,141 | 3,925 | kW-months/year | $15.32 |
Electricity Fees | $1,025 | - | $ | - |
LPG | $55,031 | 3,974 | MMBtu | $13.85 |
Fuel Oil #2 | $34,778 | 1,440 | MMBtu | $24.14 |
TOTAL ENERGY COSTS | $215,246 | |||
RECOMMENDED SAVINGS* | $48,513 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Administrative Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Administrative Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.8123 PAY UTILITY BILLS ON TIME |
Savings: $115 Cost: - |
- | - | - | - | $115 | - | - | - |
- - kWh |
- - kW-months/year |
$115 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE |
Savings: $3,774 Cost: - |
- | - | - | - | $3,774 | - | - | - |
- - kWh |
- - kW-months/year |
$3,774 - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $7,369 Cost: $18,244 |
$4,731 | 32,292 | $2,638 | 172 | - | - | - | - |
$4,731 32,292 kWh |
$2,638 172 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $3,976 Cost: $75 |
$2,553 | 17,428 | $1,423 | 93 | - | - | - | - |
$2,553 17,428 kWh |
$1,423 93 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $16,078 Cost: $1,600 |
$10,322 | 70,454 | $5,757 | 376 | - | - | - | - |
$10,322 70,454 kWh |
$5,757 376 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR |
Savings: $15,917 Cost: $51,000 |
$10,218 | 69,750 | $5,699 | 372 | - | - | - | - |
$10,218 69,750 kWh |
$5,699 372 kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7261 INSTALL TIMERS AND/OR THERMOSTATS |
Savings: $531 Cost: $2,870 |
$531 | 3,627 | - | - | - | - | - | - |
$531 3,627 kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $751 Cost: $435 |
$724 | 4,941 | - | - | - | - | $27 | - |
$724 4,941 kWh |
- - kW-months/year |
- - $ |
$27 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $48,513 Cost: $74,224 |
$29,079 | 198,491 | $15,517 | 1,013 | $3,889 | - | $27 | - | $29,079 198,491 kWh |
$15,517 1,013 kW-months/year |
$3,889 - $ |
$27 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - $ |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Administrative Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Administrative Changes | One-time Revenue or Avoided Cost |