IAC logo
IAC Assessment: UF0369
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: UF0369
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 2005
Principal Product Malt beverages
NAICS 312120 - Breweries
SIC 2082 - Malt Beverages
Sales $5,000,000-$10,000,000
# of Employees 30
Plant Area (Sq.Ft.) 45,000
Annual Production 2,000,000 Pieces
Production Hrs. Annual 3,129
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $149,328 1,649,760 kWh $0.09
Electricity Demand $38,808 420 kW-months/year $92.40
TOTAL ENERGY COSTS $188,136
RECOMMENDED SAVINGS* $34,183 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $25,003
#|Description Savings
Cost
Status Electricity Usage Electricity Usage
$ kWh
01: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$1,002
Cost:
$2,082
$1,002 15,189 $1,002
15,189
kWh
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,073
Cost:
$460
$2,073 34,551 $2,073
34,551
kWh
03: 2.2511 INSULATE BARE EQUIPMENT Savings:
$21,928
Cost:
$477
$21,928 365,459 $21,928
365,459
kWh
04: 2.7313 RECYCLE AIR FOR HEATING, VENTILATION AND AIR CONDITIONING Savings:
-
Cost:
$24,800
- - -
-
kWh
05: 2.4111 UTILIZE ENERGY-EFFICIENT BELTS AND OTHER IMPROVED MECHANISMS Savings:
$1,520
Cost:
-
$1,520 8,004 $1,520
8,004
kWh
06: 2.7251 REDUCE AIR CONDITIONING LOAD BY EVAPORATING WATER FROM ROOF Savings:
$2,471
Cost:
$900
$2,471 37,435 $2,471
37,435
kWh
07: 2.2621 MODIFY REFRIGERATION SYSTEM TO OPERATE AT A LOWER PRESSURE Savings:
$5,189
Cost:
$5,000
$5,189 68,627 $5,189
68,627
kWh
08: 4.1250 Savings:
-
Cost:
-
- - -
-
kWh
TOTAL RECOMMENDED Savings:
$34,183
Cost:
$33,719
$34,183 529,265 $34,183
529,265
kWh
TOTAL IMPLEMENTED Savings:
$25,003
Cost:
$27,819
$25,003 415,199 $25,003
415,199
kWh
Savings
Cost
$ kWh
Electricity Usage Electricity Usage