Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Florida
Assessment Year 2010
Principal Product aircraft ignition exciters
NAICS 336413 - Other Aircraft Parts and Auxiliary Equipment Manufacturing
SIC 3694 - Engine Electrical Equipment
Sales $5,000,000-$10,000,000
# of Employees 600
Plant Area (Sq.Ft.) 150,000
Annual Production 10,000 Units
Production Hrs. Annual 4,860
Location (State) FL
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $861,099 7,854,933 kWh $0.11
Electricity Demand $160,799 17,766 kW-months/year $9.05
Electricity Fees $65,259 - $ -
TOTAL ENERGY COSTS $1,087,157
RECOMMENDED SAVINGS* $135,699 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $46,408
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.7111 REDUCE ILLUMINATION TO MINIMUM NECESSARY LEVELS Savings:
$28,959
Cost:
$5,655
$28,959 288,288 - - $28,959
288,288
kWh
-
-
MMBtu
02: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$1,044
Cost:
-
$1,044 12,000 - - $1,044
12,000
kWh
-
-
MMBtu
03: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$1,531
Cost:
-
$1,531 14,051 - - $1,531
14,051
kWh
-
-
MMBtu
04: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED Savings:
$2,547
Cost:
-
$2,547 29,285 - - $2,547
29,285
kWh
-
-
MMBtu
05: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$1,211
Cost:
-
$1,211 13,925 - - $1,211
13,925
kWh
-
-
MMBtu
06: 2.2441 PREHEAT BOILER MAKEUP WATER WITH WASTE PROCESS HEAT Savings:
$86,549
Cost:
$4,000
- - $86,549 90,156 -
-
kWh
$86,549
90,156
MMBtu
07: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$7,016
Cost:
$404
$7,016 64,366 - - $7,016
64,366
kWh
-
-
MMBtu
08: 2.7228 AVOID INTRODUCING HOT, HUMID, OR DIRTY AIR INTO HVAC SYSTEM Savings:
$6,842
Cost:
-
$6,842 62,779 - - $6,842
62,779
kWh
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$135,699
Cost:
$10,059
$49,150 484,694 $86,549 90,156 $49,150
484,694
kWh
$86,549
90,156
MMBtu
TOTAL IMPLEMENTED Savings:
$46,408
Cost:
$6,059
$46,408 456,718 - - $46,408
456,718
kWh
-
-
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Natural Gas Electricity Usage Natural Gas