Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Michigan
Assessment Year 2000
Principal Product Specialty Chemicals
NAICS n/a
SIC 2800 -
Sales $50,000,000-$100,000,000
# of Employees 146
Plant Area (Sq.Ft.) 90,000
Annual Production 12,200,000 Pounds
Production Hrs. Annual 6,600
Location (State) MI
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $114,083 3,385,405 kWh $0.03
Electricity Demand $74,590 8,256 kW-months/year $9.03
Electricity Fees $11,159 - $ -
Natural Gas $57,892 15,586 MMBtu $3.71
TOTAL ENERGY COSTS $257,724
RECOMMENDED SAVINGS* $40,724 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $34,973
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Water Disposal Electricity Usage Electricity Demand Natural Gas Water Disposal
$ kWh $ kW-months/year $ MMBtu $ Tgal
01: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$575
Cost:
$500
$377 11,137 $198 20 - - - - $377
11,137
kWh
$198
20
kW-months/year
-
-
MMBtu
-
-
Tgal
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,279
Cost:
$300
$1,492 44,256 $787 81 - - - - $1,492
44,256
kWh
$787
81
kW-months/year
-
-
MMBtu
-
-
Tgal
03: 2.2136 INSTALL / REPAIR INSULATION ON STEAM LINES Savings:
$664
Cost:
$309
- - - - $664 178 - - -
-
kWh
-
-
kW-months/year
$664
178
MMBtu
-
-
Tgal
04: 2.2492 USE "HEAT WHEEL" OR OTHER HEAT EXCHANGER TO CROSS-EXCHANGE BUILDING EXHAUST AIR WITH MAKE-UP AIR Savings:
$5,751
Cost:
$18,000
- - - - $5,751 1,542 - - -
-
kWh
-
-
kW-months/year
$5,751
1,542
MMBtu
-
-
Tgal
05: 3.4115 RECOVER AND REUSE COOLING WATER Savings:
$31,455
Cost:
$21,257
- - - - - - $31,455 3,700,000 -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$31,455
3,700,000
Tgal
TOTAL RECOMMENDED Savings:
$40,724
Cost:
$40,366
$1,869 55,393 $985 101 $6,415 1,720 $31,455 3,700,000 $1,869
55,393
kWh
$985
101
kW-months/year
$6,415
1,720
MMBtu
$31,455
3,700,000
Tgal
TOTAL IMPLEMENTED Savings:
$34,973
Cost:
$22,366
$1,869 55,393 $985 101 $664 178 $31,455 3,700,000 $1,869
55,393
kWh
$985
101
kW-months/year
$664
178
MMBtu
$31,455
3,700,000
Tgal
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ Tgal
Electricity Usage Electricity Demand Natural Gas Water Disposal Electricity Usage Electricity Demand Natural Gas Water Disposal