Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Michigan
Assessment Year 2010
Principal Product Paint Mixing Products
NAICS 333249 - Other Industrial Machinery Manufacturing
SIC 3559 - Special Industry Machinery, Nec
Sales $10,000,000-$50,000,000
# of Employees 54
Plant Area (Sq.Ft.) 93,300
Annual Production 1 Units
Production Hrs. Annual 2,184
Location (State) MI
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $82,548 729,770 kWh $0.11
Natural Gas $76,224 7,912 MMBtu $9.63
TOTAL ENERGY COSTS $158,772
RECOMMENDED SAVINGS* $74,512 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Fees Natural Gas Electricity Usage Electricity Fees Natural Gas
$ kWh $ $ $ MMBtu
01: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$2,880
Cost:
$2,484
$2,880 28,069 - - - - $2,880
28,069
kWh
-
-
$
-
-
MMBtu
02: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$861
Cost:
$3,000
$861 8,396 - - - - $861
8,396
kWh
-
-
$
-
-
MMBtu
03: 2.3415 USE A FOSSIL FUEL ENGINE TO COGENERATE ELECTRICITY OR MOTIVE POWER; AND UTILIZE HEAT Savings:
$30,357
Cost:
$350,000
- - $30,357 - - - -
-
kWh
$30,357
-
$
-
-
MMBtu
04: 2.5113 USE DIRECT FLAME IMPINGEMENT OR INFRARED PROCESSING FOR CHAMBER TYPE HEATING Savings:
$21,456
Cost:
$250,000
- - - - $21,456 2,228 -
-
kWh
-
-
$
$21,456
2,228
MMBtu
05: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS Savings:
$6,024
Cost:
$14,751
- - - - $6,024 645 -
-
kWh
-
-
$
$6,024
645
MMBtu
06: 2.7234 USE HEAT PUMP FOR SPACE CONDITIONING Savings:
$7,702
Cost:
$217,800
- - - - $7,702 960 -
-
kWh
-
-
$
$7,702
960
MMBtu
07: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER Savings:
$3,245
Cost:
$5,500
- - - - $3,245 337 -
-
kWh
-
-
$
$3,245
337
MMBtu
08: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$1,714
Cost:
$1,500
- - - - $1,714 178 -
-
kWh
-
-
$
$1,714
178
MMBtu
09: 2.2442 PREHEAT COMBUSTION AIR WITH WASTE HEAT Savings:
$273
Cost:
$1,400
- - - - $273 28 -
-
kWh
-
-
$
$273
28
MMBtu
TOTAL RECOMMENDED Savings:
$74,512
Cost:
$846,435
$3,741 36,465 $30,357 - $40,414 4,376 $3,741
36,465
kWh
$30,357
-
$
$40,414
4,376
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
$
-
-
MMBtu
Savings
Cost
$ kWh $ $ $ MMBtu
Electricity Usage Electricity Fees Natural Gas Electricity Usage Electricity Fees Natural Gas