Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Michigan
Assessment Year 2015
Principal Product Metal products
NAICS 332812 - Metal Coating, Engraving (except Jewelry and Silverware), and Allied Services to Manufacturers
SIC 3499 - Fabricated Metal Products, Nec
Sales $10,000,000-$50,000,000
# of Employees 150
Plant Area (Sq.Ft.) 66,400
Annual Production 20,000,000 Pounds
Production Hrs. Annual 5,824
Location (State) MI
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $372,874 3,340,506 kWh $0.11
Natural Gas $97,507 12,869 MMBtu $7.58
TOTAL ENERGY COSTS $470,381
RECOMMENDED SAVINGS* $46,835 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $45,537
#|Description Savings
Cost
Status Electricity Usage Natural Gas Electricity Usage Natural Gas
$ kWh $ MMBtu
01: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS Savings:
$1,025
Cost:
$1,500
$1,025 9,196 - - $1,025
9,196
kWh
-
-
MMBtu
02: 2.1311 REPLACE ELECTRICALLY-OPERATED EQUIPMENT WITH FOSSIL FUEL EQUIPMENT Savings:
$21,808
Cost:
$17,500
$31,170 279,552 $(-9,362) (-1,272) $31,170
279,552
kWh
$(-9,362)
(-1,272)
MMBtu
03: 2.2711 UTILIZE OUTSIDE AIR INSTEAD OF CONDITIONED AIR FOR DRYING Savings:
$1,298
Cost:
$100
$1,298 11,648 - - $1,298
11,648
kWh
-
-
MMBtu
04: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT Savings:
$22,704
Cost:
$10,000
- - $22,704 2,995 -
-
kWh
$22,704
2,995
MMBtu
TOTAL RECOMMENDED Savings:
$46,835
Cost:
$29,100
$33,493 300,396 $13,342 1,723 $33,493
300,396
kWh
$13,342
1,723
MMBtu
TOTAL IMPLEMENTED Savings:
$45,537
Cost:
$29,000
$32,195 288,748 $13,342 1,723 $32,195
288,748
kWh
$13,342
1,723
MMBtu
Savings
Cost
$ kWh $ MMBtu
Electricity Usage Natural Gas Electricity Usage Natural Gas