Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Utah
Assessment Year 2005
Principal Product Composite Materials
NAICS 332323 - Ornamental and Architectural Metal Work Manufacturing
SIC 3446 - Architectural Metal Work
Sales $1,000,000-$5,000,000
# of Employees 20
Plant Area (Sq.Ft.) 70,000
Annual Production 300,000 Pieces
Production Hrs. Annual 2,184
Location (State) UT
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $10,762 397,560 kWh $0.03
Electricity Demand $23,255 2,307 kW-months/year $10.08
Natural Gas $12,983 1,854 MMBtu $7.00
TOTAL ENERGY COSTS $47,000
RECOMMENDED SAVINGS* $19,010 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ MMBtu $ $
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$840
Cost:
$330
$280 9,940 $560 55 - - - - $280
9,940
kWh
$560
55
kW-months/year
-
-
MMBtu
-
-
$
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM Savings:
$3,320
Cost:
$5,000
$1,100 39,100 $2,220 215 - - - - $1,100
39,100
kWh
$2,220
215
kW-months/year
-
-
MMBtu
-
-
$
03: 2.7134 USE PHOTOCELL CONTROLS Savings:
$2,530
Cost:
$2,040
$470 16,640 $2,060 200 - - - - $470
16,640
kWh
$2,060
200
kW-months/year
-
-
MMBtu
-
-
$
04: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$3,320
Cost:
$1,950
- - - - $3,320 398 - - -
-
kWh
-
-
kW-months/year
$3,320
398
MMBtu
-
-
$
05: 3.5311 RECOVER AND REUSE WASTE MATERIAL Savings:
$9,000
Cost:
-
- - - - - - $9,000 - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
$9,000
-
$
TOTAL RECOMMENDED Savings:
$19,010
Cost:
$9,320
$1,850 65,680 $4,840 470 $3,320 398 $9,000 - $1,850
65,680
kWh
$4,840
470
kW-months/year
$3,320
398
MMBtu
$9,000
-
$
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $
Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Natural Gas One-time Revenue or Avoided Cost