Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | University of Washington |
---|---|
Assessment Year | 2023 |
Principal Product | resin, fiberglass, carbon fiber |
NAICS | 336413 - Other Aircraft Parts and Auxiliary Equipment Manufacturing |
SIC | 3728 - Aircraft Parts And Equipment, Nec |
Sales | $10,000,000-$50,000,000 |
# of Employees | 230 |
Plant Area (Sq.Ft.) | 127,500 |
Annual Production | 3,000 Units |
Production Hrs. Annual | 7,722 |
Location (State) | WA |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $292,365 | 3,617,400 | kWh | $0.08 |
Electricity Demand | $108,360 | 17,665 | kW-months/year | $6.13 |
Electricity Fees | $60,444 | - | $ | - |
Natural Gas | $80,548 | 6,485 | MMBtu | $12.42 |
TOTAL ENERGY COSTS | $541,717 | |||
RECOMMENDED SAVINGS* | $843,540 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | - |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Primary Product | Electricity Usage | Electricity Demand | Natural Gas | Primary Product | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7491 INSULATE GLAZING, WALLS, CEILINGS, AND ROOFS |
Savings: $56,470 Cost: $23,651 |
$52,344 | 451,241 | $3,794 | 618 | $332 | 27 | - | - |
$52,344 451,241 kWh |
$3,794 618 kW-months/year |
$332 27 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $18,837 Cost: $2,080 |
$17,402 | 150,015 | $1,435 | 234 | - | - | - | - |
$17,402 150,015 kWh |
$1,435 234 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $1,001 Cost: $2,820 |
- | - | - | - | $1,001 | 81 | - | - |
- - kWh |
- - kW-months/year |
$1,001 81 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2622 REPLACE EXISTING CHILLER WITH HIGH EFFICIENCY MODEL |
Savings: $11,443 Cost: $68,000 |
$10,670 | 91,980 | $773 | 126 | - | - | - | - |
$10,670 91,980 kWh |
$773 126 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $5,789 Cost: $3,000 |
$5,348 | 46,106 | $441 | 72 | - | - | - | - |
$5,348 46,106 kWh |
$441 72 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.3142 USER BATTERY STORAGE FOR POWER QUALITY ISSUES |
Savings: $750,000 Cost: $871,000 |
- | - | - | - | - | - | $750,000 | - |
- - kWh |
- - kW-months/year |
- - MMBtu |
$750,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $843,540 Cost: $970,551 |
$85,764 | 739,342 | $6,443 | 1,050 | $1,333 | 107 | $750,000 | - | $85,764 739,342 kWh |
$6,443 1,050 kW-months/year |
$1,333 107 MMBtu |
$750,000 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: - Cost: - |
- | - | - | - | - | - | - | - | - - kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Primary Product | Electricity Usage | Electricity Demand | Natural Gas | Primary Product |