Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center University of Washington
Assessment Year 2024
Principal Product Other Metal Valve and Pipe Fitting Manufacturing
NAICS 332919 - Other Metal Valve and Pipe Fitting Manufacturing
SIC 3494 - Valves And Pipe Fittings, Nec
Sales $100,000,000-$500,000,000
# of Employees 150
Plant Area (Sq.Ft.) 508,900
Annual Production 23,000,000 Units
Production Hrs. Annual 5,200
Location (State) WA
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $1,067,720 18,241,589 kWh $0.06
Electricity Demand $365,215 76,740 kW-months/year $4.76
Electricity Fees $86,325 - $ -
Natural Gas $129,490 13,163 MMBtu $9.84
TOTAL ENERGY COSTS $1,648,750
RECOMMENDED SAVINGS* $295,018 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* -
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Electricity Usage Electricity Demand Natural Gas
$ kWh $ kW-months/year $ MMBtu
01: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$25,580
Cost:
$25,000
$21,537 386,160 $4,043 850 - - $21,537
386,160
kWh
$4,043
850
kW-months/year
-
-
MMBtu
02: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$2,204
Cost:
$4,593
$2,204 37,674 - - - - $2,204
37,674
kWh
-
-
kW-months/year
-
-
MMBtu
03: 2.7273 INSTALL DESICCANT HUMIDITY CONTROL SYSTEM Savings:
$29,790
Cost:
$91,000
$(-371) (-6,336) - - $30,161 3,066 $(-371)
(-6,336)
kWh
-
-
kW-months/year
$30,161
3,066
MMBtu
04: 2.4226 USE / PURCHASE OPTIMUM SIZED COMPRESSOR Savings:
$234,799
Cost:
$127,331
$210,690 3,601,531 $24,109 5,028 - - $210,690
3,601,531
kWh
$24,109
5,028
kW-months/year
-
-
MMBtu
05: 2.7134 USE PHOTOCELL CONTROLS Savings:
$913
Cost:
$1,908
$913 15,600 - - - - $913
15,600
kWh
-
-
kW-months/year
-
-
MMBtu
06: 2.7447 INSTALL VINYL STRIP / HIGH SPEED / AIR CURTAIN DOORS Savings:
$1,732
Cost:
$14,382
$1,732 29,600 - - - - $1,732
29,600
kWh
-
-
kW-months/year
-
-
MMBtu
TOTAL RECOMMENDED Savings:
$295,018
Cost:
$264,214
$236,705 4,064,229 $28,152 5,878 $30,161 3,066 $236,705
4,064,229
kWh
$28,152
5,878
kW-months/year
$30,161
3,066
MMBtu
TOTAL IMPLEMENTED Savings:
-
Cost:
-
- - - - - - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
Savings
Cost
$ kWh $ kW-months/year $ MMBtu