Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2011 |
Principal Product | aircraft de-icing systems |
NAICS | 336413 - Other Aircraft Parts and Auxiliary Equipment Manufacturing |
SIC | 3728 - Aircraft Parts And Equipment, Nec |
Sales | $100,000,000-$500,000,000 |
# of Employees | 370 |
Plant Area (Sq.Ft.) | 14,700 |
Annual Production | 115,000,000 Pieces |
Production Hrs. Annual | 8,760 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $125,492 | 4,899,679 | kWh | $0.03 |
Electricity Demand | $137,023 | 12,419 | kW-months/year | $11.03 |
Natural Gas | $331,669 | 27,472 | MMBtu | $12.07 |
TOTAL ENERGY COSTS | $594,184 | |||
RECOMMENDED SAVINGS* | $35,318 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $9,833 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $19,052 Cost: $63,760 |
$(-19) | (-756) | $(-132) | (-12) | $19,203 | 1,591 |
$(-19) (-756) kWh |
$(-132) (-12) kW-months/year |
$19,203 1,591 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.2414 USE WASTE HEAT FROM HOT FLUE GASES TO PREHEAT |
Savings: $6,433 Cost: $8,495 |
- | - | - | - | $6,433 | 533 |
- - kWh |
- - kW-months/year |
$6,433 533 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $4,569 Cost: $14,510 |
$2,876 | 111,398 | $1,693 | 153 | - | - |
$2,876 111,398 kWh |
$1,693 153 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT |
Savings: $4,500 Cost: $4,500 |
- | - | - | - | $4,500 | 324 |
- - kWh |
- - kW-months/year |
$4,500 324 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $764 Cost: $480 |
$411 | 15,991 | $353 | 32 | - | - |
$411 15,991 kWh |
$353 32 kW-months/year |
- - MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $35,318 Cost: $91,745 |
$3,268 | 126,633 | $1,914 | 173 | $30,136 | 2,448 | $3,268 126,633 kWh |
$1,914 173 kW-months/year |
$30,136 2,448 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $9,833 Cost: $19,490 |
$3,287 | 127,389 | $2,046 | 185 | $4,500 | 324 | $3,287 127,389 kWh |
$2,046 185 kW-months/year |
$4,500 324 MMBtu |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Electricity Usage | Electricity Demand | Natural Gas |