Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | West Virginia University |
---|---|
Assessment Year | 2023 |
Principal Product | Custom Cabinetry |
NAICS | 337110 - Wood Kitchen Cabinet and Countertop Manufacturing |
SIC | 2434 - Wood Kitchen Cabinets |
Sales | $10,000,000-$50,000,000 |
# of Employees | 80 |
Plant Area (Sq.Ft.) | 970,000 |
Annual Production | 5,100 Pieces |
Production Hrs. Annual | 4,590 |
Location (State) | WV |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $42,475 | 834,390 | kWh | $0.05 |
Electricity Demand | $42,141 | 2,857 | kW-months/year | $14.75 |
Electricity Fees | $3,640 | - | $ | - |
LPG | $54,405 | 2,647 | MMBtu | $20.55 |
TOTAL ENERGY COSTS | $143,638 | |||
RECOMMENDED SAVINGS* | $41,030 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $7,373 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | LPG | Personnel Changes | Electricity Usage | Electricity Demand | LPG | Personnel Changes | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $23,558 Cost: $12,360 |
$13,779 | 254,701 | $9,779 | 663 | - | - | - | - |
$13,779 254,701 kWh |
$9,779 663 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4146 USE ADJUSTABLE FREQUENCY DRIVE OR MULTIPLE SPEED MOTORS ON EXISTING SYSTEM |
Savings: $6,092 Cost: $29,560 |
$556 | 10,272 | $398 | 27 | $5,138 | 250 | - | - |
$556 10,272 kWh |
$398 27 kW-months/year |
$5,138 250 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.1233 ANALYZE FLUE GAS FOR PROPER AIR/FUEL RATIO |
Savings: $4,500 Cost: $1,023 |
- | - | - | - | $4,500 | 219 | - | - |
- - kWh |
- - kW-months/year |
$4,500 219 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.2449 RECOVER HEAT FROM EXHAUSTED STEAM, HOT AIR OR HOT WATER |
Savings: $4,007 Cost: $10,420 |
- | - | - | - | $4,007 | 195 | - | - |
- - kWh |
- - kW-months/year |
$4,007 195 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4224 UPGRADE CONTROLS ON COMPRESSORS |
Savings: $954 Cost: $1,965 |
$836 | 15,462 | $118 | 8 | - | - | - | - |
$836 15,462 kWh |
$118 8 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $530 Cost: $100 |
$309 | 5,707 | $221 | 15 | - | - | - | - |
$309 5,707 kWh |
$221 15 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.4221 INSTALL COMPRESSOR AIR INTAKES IN COOLEST LOCATIONS |
Savings: $523 Cost: $1,573 |
$269 | 4,964 | $192 | 13 | $62 | 3 | - | - |
$269 4,964 kWh |
$192 13 kW-months/year |
$62 3 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $459 Cost: $1,293 |
$263 | 4,864 | $196 | 13 | - | - | - | - |
$263 4,864 kWh |
$196 13 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
09: 2.4151 DEVELOP A REPAIR/REPLACE POLICY |
Savings: $310 Cost: $592 |
$200 | 3,695 | $148 | 10 | - | - | $(-38) | - |
$200 3,695 kWh |
$148 10 kW-months/year |
- - MMBtu |
$(-38) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
10: 2.6231 UTILIZE CONTROLS TO OPERATE EQUIPMENT ONLY WHEN NEEDED |
Savings: $76 Cost: $368 |
$46 | 841 | $30 | 2 | - | - | - | - |
$46 841 kWh |
$30 2 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
11: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $21 Cost: $31 |
- | - | - | - | $21 | 1 | - | - |
- - kWh |
- - kW-months/year |
$21 1 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $41,030 Cost: $59,285 |
$16,258 | 300,506 | $11,082 | 751 | $13,728 | 668 | $(-38) | - | $16,258 300,506 kWh |
$11,082 751 kW-months/year |
$13,728 668 MMBtu |
$(-38) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $7,373 Cost: $6,945 |
$1,923 | 35,533 | $905 | 61 | $4,583 | 223 | $(-38) | - | $1,923 35,533 kWh |
$905 61 kW-months/year |
$4,583 223 MMBtu |
$(-38) - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | LPG | Personnel Changes | Electricity Usage | Electricity Demand | LPG | Personnel Changes |