Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Texas A&M, College Station
Assessment Year 2001
Principal Product Wood and laminate cabinet doors and drawer fronts
NAICS n/a
SIC 2431 - Millwork
Sales $50,000,000-$100,000,000
# of Employees 750
Plant Area (Sq.Ft.) 170,000
Annual Production 3,374,800 Pieces
Production Hrs. Annual 4,376
Location (State) TX
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $245,842 6,914,358 kWh $0.04
Electricity Demand $140,679 18,506 kW-months/year $7.60
Electricity Fees $164 - $ -
Natural Gas $25,950 5,139 MMBtu $5.05
TOTAL ENERGY COSTS $412,635
RECOMMENDED SAVINGS* $19,550 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $8,510
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes
$ kWh $ kW-months/year $ MMBtu $ $ $ $
01: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED Savings:
$8,760
Cost:
$50
$3,960 141,300 $4,800 387 - - - - - - $3,960
141,300
kWh
$4,800
387
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,830
Cost:
$100
$2,830 101,000 - - - - - - - - $2,830
101,000
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
03: 2.6218 TURN OFF EQUIPMENT WHEN NOT IN USE Savings:
$2,240
Cost:
-
$2,240 80,300 - - - - - - - - $2,240
80,300
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
04: 2.8121 APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES Savings:
$1,980
Cost:
$3,960
- - - - - - - - $1,980 - -
-
kWh
-
-
kW-months/year
-
-
MMBtu
-
-
$
$1,980
-
$
05: 2.2437 RECOVER WASTE HEAT FROM EQUIPMENT Savings:
$1,460
Cost:
$500
- - - - $1,460 290 - - - - -
-
kWh
-
-
kW-months/year
$1,460
290
MMBtu
-
-
$
-
-
$
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$860
Cost:
$540
$100 3,440 $60 5 - - $700 - - - $100
3,440
kWh
$60
5
kW-months/year
-
-
MMBtu
$700
-
$
-
-
$
07: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$850
Cost:
$1,910
$230 8,280 $620 50 - - - - - - $230
8,280
kWh
$620
50
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
08: 2.4314 USE SYNTHETIC LUBRICANT Savings:
$390
Cost:
-
$290 10,300 $100 8 - - - - - - $290
10,300
kWh
$100
8
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
09: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$180
Cost:
$280
$80 2,760 $100 8 - - - - - - $80
2,760
kWh
$100
8
kW-months/year
-
-
MMBtu
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$19,550
Cost:
$7,340
$9,730 347,380 $5,680 458 $1,460 290 $700 - $1,980 - $9,730
347,380
kWh
$5,680
458
kW-months/year
$1,460
290
MMBtu
$700
-
$
$1,980
-
$
TOTAL IMPLEMENTED Savings:
$8,510
Cost:
$4,560
$5,070 181,300 - - $1,460 290 - - $1,980 - $5,070
181,300
kWh
-
-
kW-months/year
$1,460
290
MMBtu
-
-
$
$1,980
-
$
Savings
Cost
$ kWh $ kW-months/year $ MMBtu $ $ $ $
Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes Electricity Usage Electricity Demand Natural Gas Personnel Changes Administrative Changes