Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Texas A&M, College Station |
---|---|
Assessment Year | 2008 |
Principal Product | Envelopes |
NAICS | 322230 - Stationery Product Manufacturing |
SIC | 2677 - Envelopes |
Sales | $10,000,000-$50,000,000 |
# of Employees | 145 |
Plant Area (Sq.Ft.) | 114,702 |
Annual Production | 2,147,483,647 Pieces |
Production Hrs. Annual | 8,496 |
Location (State) | TX |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $653,326 | 8,466,418 | kWh | $0.08 |
Electricity Demand | $113,500 | 16,629 | kW-months/year | $6.83 |
Electricity Fees | $12,050 | - | $ | - |
TOTAL ENERGY COSTS | $778,876 | |||
RECOMMENDED SAVINGS* | $90,670 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $90,670 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $27,200 Cost: $42,370 |
$24,050 | 316,400 | $3,150 | 456 | - | - | - | - | - | - |
$24,050 316,400 kWh |
$3,150 456 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $26,350 Cost: $2,500 |
$23,300 | 306,600 | $3,050 | 442 | - | - | - | - | - | - |
$23,300 306,600 kWh |
$3,050 442 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $16,810 Cost: - |
$14,140 | 186,100 | $2,670 | 387 | - | - | - | - | - | - |
$14,140 186,100 kWh |
$2,670 387 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.7232 REPLACE EXISTING HVAC UNIT WITH HIGH EFFICIENCY MODEL |
Savings: $10,200 Cost: $24,000 |
$10,200 | 134,000 | - | - | - | - | - | - | - | - |
$10,200 134,000 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.8123 PAY UTILITY BILLS ON TIME |
Savings: $6,800 Cost: - |
- | - | - | - | $6,800 | - | - | - | - | - |
- - kWh |
- - kW-months/year |
$6,800 - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.4314 USE SYNTHETIC LUBRICANT |
Savings: $1,885 Cost: - |
$1,670 | 21,915 | $215 | 31 | - | - | - | - | - | - |
$1,670 21,915 kWh |
$215 31 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 3.7132 REUSE RAGS UNTIL COMPLETELY SOILED |
Savings: $1,040 Cost: - |
- | - | - | - | - | - | - | - | $1,040 | - |
- - kWh |
- - kW-months/year |
- - $ |
- - $ |
$1,040 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $385 Cost: - |
$75 | 980 | $5 | 1 | - | - | $305 | - | - | - |
$75 980 kWh |
$5 1 kW-months/year |
- - $ |
$305 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $90,670 Cost: $68,870 |
$73,435 | 965,995 | $9,090 | 1,317 | $6,800 | - | $305 | - | $1,040 | - | $73,435 965,995 kWh |
$9,090 1,317 kW-months/year |
$6,800 - $ |
$305 - $ |
$1,040 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $90,670 Cost: $68,870 |
$73,435 | 965,995 | $9,090 | 1,317 | $6,800 | - | $305 | - | $1,040 | - | $73,435 965,995 kWh |
$9,090 1,317 kW-months/year |
$6,800 - $ |
$305 - $ |
$1,040 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Ancillary Material Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | Ancillary Material Cost |