Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Texas A&M, College Station |
---|---|
Assessment Year | 2008 |
Principal Product | Asphalt roofing shingles |
NAICS | 324122 - Asphalt Shingle and Coating Materials Manufacturing |
SIC | 2952 - Asphalt Felts And Coatings |
Sales | $50,000,000-$100,000,000 |
# of Employees | 84 |
Plant Area (Sq.Ft.) | 131,300 |
Annual Production | 150,000 Thousand Feet |
Production Hrs. Annual | 7,968 |
Location (State) | TX |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $608,882 | 6,814,179 | kWh | $0.09 |
Electricity Demand | $109,063 | 13,332 | kW-months/year | $8.18 |
Electricity Fees | $2,692 | - | $ | - |
Natural Gas | $672,391 | 90,923 | MMBtu | $7.40 |
TOTAL ENERGY COSTS | $1,393,028 | |||
RECOMMENDED SAVINGS* | $161,620 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $141,730 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.4239 ELIMINATE OR REDUCE COMPRESSED AIR USAGE |
Savings: $80,000 Cost: $960 |
$80,000 | 930,000 | - | - | - | - | - | - |
$80,000 930,000 kWh |
- - kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $24,080 Cost: $1,500 |
$20,900 | 243,000 | $3,180 | 446 | - | - | - | - |
$20,900 243,000 kWh |
$3,180 446 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.4324 REPLACE HYDRAULIC / PNEUMATIC EQUIPMENT WITH ELECTRIC EQUIPMENT |
Savings: $19,260 Cost: $80,000 |
$16,700 | 195,000 | $2,560 | 360 | - | - | - | - |
$16,700 195,000 kWh |
$2,560 360 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $19,840 Cost: $30,650 |
- | - | $19,840 | 2,787 | - | - | - | - |
- - kWh |
$19,840 2,787 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $12,380 Cost: - |
$10,750 | 125,000 | $1,630 | 229 | - | - | - | - |
$10,750 125,000 kWh |
$1,630 229 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7124 MAKE A PRACTICE OF TURNING OFF LIGHTS WHEN NOT NEEDED |
Savings: $4,970 Cost: $500 |
$3,790 | 44,100 | $1,180 | 166 | - | - | - | - |
$3,790 44,100 kWh |
$1,180 166 kW-months/year |
- - MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $630 Cost: $800 |
- | - | - | - | $630 | 86 | - | - |
- - kWh |
- - kW-months/year |
$630 86 MMBtu |
- - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
08: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $460 Cost: $325 |
$110 | 1,260 | $14 | 2 | - | - | $336 | - |
$110 1,260 kWh |
$14 2 kW-months/year |
- - MMBtu |
$336 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $161,620 Cost: $114,735 |
$132,250 | 1,538,360 | $28,404 | 3,990 | $630 | 86 | $336 | - | $132,250 1,538,360 kWh |
$28,404 3,990 kW-months/year |
$630 86 MMBtu |
$336 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $141,730 Cost: $33,935 |
$115,550 | 1,343,360 | $25,844 | 3,630 | - | - | $336 | - | $115,550 1,343,360 kWh |
$25,844 3,630 kW-months/year |
- - MMBtu |
$336 - $ |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | MMBtu | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost | Electricity Usage | Electricity Demand | Natural Gas | Ancillary Material Cost |