Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Texas A&M, College Station |
---|---|
Assessment Year | 2015 |
Principal Product | Rough terrain forklifts |
NAICS | 333924 - Industrial Truck, Tractor, Trailer, and Stacker Machinery Manufacturing |
SIC | 3537 - Industrial Trucks And Tractors |
Sales | $50,000,000-$100,000,000 |
# of Employees | 174 |
Plant Area (Sq.Ft.) | 140,000 |
Annual Production | 984 Pieces |
Production Hrs. Annual | 4,020 |
Location (State) | TX |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $143,142 | 2,105,921 | kWh | $0.07 |
Electricity Demand | $29,435 | 6,312 | kW-months/year | $4.66 |
Electricity Fees | $8,772 | - | $ | - |
Natural Gas | $23,147 | 2,682 | MMBtu | $8.63 |
TOTAL ENERGY COSTS | $204,496 | |||
RECOMMENDED SAVINGS* | $64,797 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $61,992 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $23,570 Cost: $130,700 |
$20,920 | 294,600 | $2,650 | 883 | - | - | - | - | - | - |
$20,920 294,600 kWh |
$2,650 883 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7228 AVOID INTRODUCING HOT, HUMID, OR DIRTY AIR INTO HVAC SYSTEM |
Savings: $22,000 Cost: $1,140 |
$22,000 | 310,500 | - | - | - | - | - | - | - | - |
$22,000 310,500 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $3,460 Cost: $7,200 |
$3,460 | 48,710 | - | - | - | - | - | - | - | - |
$3,460 48,710 kWh |
- - kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4231 REDUCE THE PRESSURE OF COMPRESSED AIR TO THE MINIMUM REQUIRED |
Savings: $2,805 Cost: $23 |
$2,436 | 34,734 | $369 | 123 | - | - | - | - | - | - |
$2,436 34,734 kWh |
$369 123 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.8121 APPLY FOR TAX-FREE STATUS FOR ENERGY PURCHASES |
Savings: $10,875 Cost: $3,000 |
- | - | - | - | $2,175 | - | - | - | $8,700 | - |
- - kWh |
- - kW-months/year |
$2,175 - $ |
- - $ |
$8,700 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $1,433 Cost: $469 |
$445 | 6,264 | $29 | 10 | - | - | $959 | - | - | - |
$445 6,264 kWh |
$29 10 kW-months/year |
- - $ |
$959 - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
07: 2.7122 DISCONNECT BALLASTS |
Savings: $654 Cost: $79 |
$513 | 7,233 | $141 | 47 | - | - | - | - | - | - |
$513 7,233 kWh |
$141 47 kW-months/year |
- - $ |
- - $ |
- - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $64,797 Cost: $142,611 |
$49,774 | 702,041 | $3,189 | 1,063 | $2,175 | - | $959 | - | $8,700 | - | $49,774 702,041 kWh |
$3,189 1,063 kW-months/year |
$2,175 - $ |
$959 - $ |
$8,700 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $61,992 Cost: $142,588 |
$47,338 | 667,307 | $2,820 | 940 | $2,175 | - | $959 | - | $8,700 | - | $47,338 667,307 kWh |
$2,820 940 kW-months/year |
$2,175 - $ |
$959 - $ |
$8,700 - $ |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | $ | $ | $ | $ | $ | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost | Electricity Usage | Electricity Demand | Electricity Fees | Personnel Changes | One-time Revenue or Avoided Cost |