Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center | Texas A&M, College Station |
---|---|
Assessment Year | 2017 |
Principal Product | Mechanical cable controls and pedals for industrial applications |
NAICS | 335314 - Relay and Industrial Control Manufacturing |
SIC | 3625 - Relays And Industrial Controls |
Sales | $10,000,000-$50,000,000 |
# of Employees | 109 |
Plant Area (Sq.Ft.) | 78,000 |
Annual Production | 12,000,000 Pieces |
Production Hrs. Annual | 2,008 |
Location (State) | TX |
Source | Yearly Cost | Usage | Unit | Unit Cost |
---|---|---|---|---|
Electricity Usage | $88,082 | 1,659,146 | kWh | $0.05 |
Electricity Demand | $57,438 | 5,093 | kW-months/year | $11.28 |
Electricity Fees | $3,825 | - | $ | - |
Natural Gas | $1,824 | 282 | MMBtu | $6.47 |
TOTAL ENERGY COSTS | $151,169 | |||
RECOMMENDED SAVINGS* | $28,635 | *Non-energy impacts included in savings. See recommendations below |
||
IMPLEMENTED SAVINGS* | $24,865 |
#|Description |
Savings Cost |
Status | Electricity Usage | Electricity Demand | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Solid Waste (non-haz) | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
$ | kWh | $ | kW-months/year | $ | lb | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
01: 3.5212 REGRIND, REUSE, OR SELL SCRAP PLASTIC PARTS |
Savings: $6,900 Cost: - |
- | - | - | - | $6,900 | 27,610 |
- - kWh |
- - kW-months/year |
$6,900 27,610 lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
02: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS |
Savings: $10,965 Cost: $28,840 |
$4,815 | 96,300 | $6,150 | 510 | - | - |
$4,815 96,300 kWh |
$6,150 510 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
03: 2.3212 OPTIMIZE PLANT POWER FACTOR |
Savings: $3,490 Cost: $3,740 |
- | - | $3,490 | 288 | - | - |
- - kWh |
$3,490 288 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES |
Savings: $2,930 Cost: $1,000 |
$1,200 | 24,100 | $1,730 | 144 | - | - |
$1,200 24,100 kWh |
$1,730 144 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
05: 2.2511 INSULATE BARE EQUIPMENT |
Savings: $3,770 Cost: $1,000 |
$1,540 | 30,800 | $2,230 | 185 | - | - |
$1,540 30,800 kWh |
$2,230 185 kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
06: 2.7135 INSTALL OCCUPANCY SENSORS |
Savings: $580 Cost: $220 |
$580 | 11,675 | - | - | - | - |
$580 11,675 kWh |
- - kW-months/year |
- - lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL RECOMMENDED |
Savings: $28,635 Cost: $34,800 |
$8,135 | 162,875 | $13,600 | 1,127 | $6,900 | 27,610 | $8,135 162,875 kWh |
$13,600 1,127 kW-months/year |
$6,900 27,610 lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
TOTAL IMPLEMENTED |
Savings: $24,865 Cost: $33,800 |
$6,595 | 132,075 | $11,370 | 942 | $6,900 | 27,610 | $6,595 132,075 kWh |
$11,370 942 kW-months/year |
$6,900 27,610 lb |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Savings Cost |
$ | kWh | $ | kW-months/year | $ | lb | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Electricity Usage | Electricity Demand | Solid Waste (non-haz) | Electricity Usage | Electricity Demand | Solid Waste (non-haz) |