IAC logo
IAC Assessment: AM0843
Sponsored by:
DOE MESC
IAC logo
IAC Assessment: AM0843
Implementation Grant Funding Opportunity Open
IMPORTANT: The grant program operates on a rolling basis and applications may be submitted at any time, with quarterly reviews.
Learn More
Implementation Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received IAC or Combined Heat and Power Technical Assistance Partnership assessments between 2018 and 2024, can now apply for grants for implementation of assessment recommendations up 50% of qualifying* project costs with a maximum of $300,000 per manufacturer.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
IAC Center Texas A&M, College Station
Assessment Year 2022
Principal Product Conveyors
NAICS 333922 - Conveyor and Conveying Equipment Manufacturing
SIC 3535 - Conveyors And Conveying Equipment
Sales $10,000,000-$50,000,000
# of Employees 140
Plant Area (Sq.Ft.) 120,000
Annual Production 200,000,000 Tons
Production Hrs. Annual 2,754
Location (State) TX
Source Yearly Cost Usage Unit Unit Cost
Electricity Usage $56,320 1,583,207 kWh $0.04
Electricity Demand $72,577 11,090 kW-months/year $6.54
Electricity Fees $4,611 - $ -
TOTAL ENERGY COSTS $133,508
RECOMMENDED SAVINGS* $43,672 *Non-energy impacts
included in savings.
See recommendations below
IMPLEMENTED SAVINGS* $228
#|Description Savings
Cost
Status Electricity Usage Electricity Demand Electricity Fees Ancillary Material Cost One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Electricity Fees Ancillary Material Cost One-time Revenue or Avoided Cost
$ kWh $ kW-months/year $ $ $ $ $ $
01: 2.3212 OPTIMIZE PLANT POWER FACTOR Savings:
$18,385
Cost:
$33,511
- - $18,385 2,811 - - - - - - -
-
kWh
$18,385
2,811
kW-months/year
-
-
$
-
-
$
-
-
$
02: 2.8114 CHANGE RATE SCHEDULES OR OTHER CHANGES IN UTILITY SERVICE Savings:
$12,030
Cost:
$110
- - - - - - - - $12,030 - -
-
kWh
-
-
kW-months/year
-
-
$
-
-
$
$12,030
-
$
03: 2.8112 COMBINE UTILITY METERS Savings:
$7,115
Cost:
$4,500
- - $4,775 730 $2,340 - - - - - -
-
kWh
$4,775
730
kW-months/year
$2,340
-
$
-
-
$
-
-
$
04: 2.4236 ELIMINATE LEAKS IN INERT GAS AND COMPRESSED AIR LINES/ VALVES Savings:
$2,975
Cost:
$3,000
$1,425 40,720 $1,550 237 - - - - - - $1,425
40,720
kWh
$1,550
237
kW-months/year
-
-
$
-
-
$
-
-
$
05: 2.8117 INSTALL SUB-METERING EQUIPMENT Savings:
$2,741
Cost:
$500
$2,741 78,304 - - - - - - - - $2,741
78,304
kWh
-
-
kW-months/year
-
-
$
-
-
$
-
-
$
06: 2.7142 UTILIZE HIGHER EFFICIENCY LAMPS AND/OR BALLASTS Savings:
$228
Cost:
$1,190
$130 3,640 $100 16 - - $(-2) - - - $130
3,640
kWh
$100
16
kW-months/year
-
-
$
$(-2)
-
$
-
-
$
07: 2.7135 INSTALL OCCUPANCY SENSORS Savings:
$18
Cost:
$84
$18 505 - - - - - - - - $18
505
kWh
-
-
kW-months/year
-
-
$
-
-
$
-
-
$
08: 2.6212 TURN OFF EQUIPMENT DURING BREAKS, REDUCE OPERATING TIME Savings:
$180
Cost:
$160
$180 5,145 - - - - - - - - $180
5,145
kWh
-
-
kW-months/year
-
-
$
-
-
$
-
-
$
TOTAL RECOMMENDED Savings:
$43,672
Cost:
$43,055
$4,494 128,314 $24,810 3,794 $2,340 - $(-2) - $12,030 - $4,494
128,314
kWh
$24,810
3,794
kW-months/year
$2,340
-
$
$(-2)
-
$
$12,030
-
$
TOTAL IMPLEMENTED Savings:
$228
Cost:
$1,190
$130 3,640 $100 16 - - $(-2) - - - $130
3,640
kWh
$100
16
kW-months/year
-
-
$
$(-2)
-
$
-
-
$
Savings
Cost
$ kWh $ kW-months/year $ $ $ $ $ $
Electricity Usage Electricity Demand Electricity Fees Ancillary Material Cost One-time Revenue or Avoided Cost Electricity Usage Electricity Demand Electricity Fees Ancillary Material Cost One-time Revenue or Avoided Cost